How it’s calculated
- R
- Horizontal Buried Grounding Conductor Resistance · Ω / mΩ / kΩ / MΩ
- ρ
- Soil Resistivity · Ω·m / Ω·cm / Ω·mm²/m / µΩ·cm
- L
- Buried Conductor Length · m / ft / in / yd
- s
- Burial Depth · m / ft / in / yd
- d
- Conductor Diameter · mm / in / cm / m
Questions
What is the formula for horizontal buried grounding conductor resistance and what does each variable mean?
The governing equation is R = (ρ / (π · L)) · ln(2L / √(2s · d)), solving for R from ρ (soil resistivity, Ω·m), L (buried conductor length, m), s (burial depth, m) and d (conductor diameter, mm). Earthing resistance of bare horizontal copper counterpoise or trench-buried grounding wire at depth s.
Which input and output units can you select for horizontal buried grounding conductor resistance?
Every parameter includes metric and imperial unit selectors: ρ [Ω·m, Ω·cm, Ω·mm²/m, µΩ·cm, Ω·cmil/ft]; L [m, ft, in, yd, mi, km, cm, mm]; s [m, ft, in, yd, mi, km, cm, mm]; d [mm, in, cm, m, mil]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output R across Ω, mΩ, kΩ, MΩ, µΩ.
When is the horizontal buried grounding conductor resistance formula used in electrical engineering?
Confirm that the protective device clears both sustained overloads and bolted faults within the conductor thermal withstand time while maintaining bonding continuity and upstream selectivity.