How it’s calculated
EV chargers are continuous loads (125% rule): a 32 A charger (7.7 kW) requires a 40 A breaker and 8 AWG (10 mm²) copper; a 48 A hardwired charger (11.5 kW) requires a 60 A breaker and 6 AWG (16 mm²); a 3-phase 11 kW wallbox (16 A/phase) uses a 20 A 3-pole breaker and 2.5–4 mm² copper.
Questions
What wire size and breaker do I need for a 48 A or 40 A Level 2 EV charger?
Under NEC 625.41 (125% continuous duty): a 32 A EVSE needs a 40 A breaker and 8 AWG copper; a 40 A EVSE needs a 50 A breaker and 6 AWG copper; a 48 A EVSE must be hardwired on a 60 A breaker with 6 AWG THHN in conduit (or 4 AWG NM-B).
What RCD / GFCI type does an EV charger require?
EV chargers can produce smooth DC leakage that blinds standard AC RCDs. Use a 30 mA Type A RCD when the EVSE has built-in 6 mA DC fault detection (IEC 62955), or a Type B RCD otherwise; under NEC plug-in receptacles also require GFCI protection.