Air Conditioner: Amps, Breaker & Wire

Turn the unit’s BTU rating into amps and get the recommended breaker and copper wire size under both NEC (AWG) and IEC (mm²) criteria.

Technology
Supply
—

Enter your values to calculate instantly.

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

Quick chart: inverter air conditioner by BTU (single-phase)

CapacityApprox. electrical inputCurrent @ 220 VCurrent @ 115 VBreaker @ 220 V (NEC · IEC)Cu wire @ 220 V
9 000 BTU/h (0.75 TR)720 W3.4 A6.6 A15 A · 10 A14 AWG · 1.5 mm²
12 000 BTU/h (1 TR)960 W4.6 A8.8 A15 A · 10 A14 AWG · 1.5 mm²
18 000 BTU/h (1.5 TR)1440 W6.9 A13.2 A15 A · 10 A14 AWG · 1.5 mm²
24 000 BTU/h (2 TR)1920 W9.2 A17.6 A15 A · 16 A14 AWG · 2.5 mm²
36 000 BTU/h (3 TR)2880 W13.8 A—20 A · 20 A12 AWG · 2.5 mm²
48 000 BTU/h (4 TR)3840 W18.4 A—25 A · 25 A10 AWG · 4 mm²
60 000 BTU/h (5 TR)4800 W23 A—30 A · 32 A10 AWG · 6 mm²

How it’s calculated

A 12,000 BTU inverter mini-split at 230 V draws roughly 4–6 A, so a dedicated 15 A circuit with 14 AWG copper is typically enough. The nameplate always rules: the circuit must meet its MCA and the breaker must not exceed its MOP.

Pe=QBTU/hEERP_e = \dfrac{Q_{BTU/h}}{EER}
Electrical input power
I=PeV⋅FPI = \dfrac{P_e}{V \cdot FP}
Running current (single-phase)
IMCA=1,25⋅II_{MCA} = 1{,}25 \cdot I
Minimum circuit ampacity

Questions

What size breaker for a 12,000 BTU air conditioner?

A 12,000 BTU inverter unit at 230 V draws about 4–5 A, so a 15 A breaker on a dedicated circuit is enough. At 115 V the current roughly doubles (≈ 9–12 A) and a 20 A breaker with 12 AWG wire is typical. Always check the nameplate MOP.

What wire size does a 24,000 BTU air conditioner need?

At 230 V a 24,000 BTU inverter draws ≈ 9–10 A (MCA ≈ 12 A): 14–12 AWG copper with a 15–20 A breaker. Fixed-speed units draw ≈ 25 % more, so 12 AWG is the safer pick. On long runs, check voltage drop.

How many watts does an air conditioner use?

Roughly BTU/h ÷ EER. With a typical EER of 12.5 (inverter) a 12,000 BTU unit draws ≈ 960 W; a fixed-speed unit with EER 10 draws about 1,200 W. Real monthly usage depends on compressor run time.

Can I plug the air conditioner into a regular outlet?

Mini-splits and larger window units should be on a dedicated circuit with their own breaker. Sharing a circuit causes nuisance trips, hot receptacles and voltage drop that stresses the compressor.