Breaker Parameters

Interruption capacities (Icu, Ics), operating voltage and trip adjustment of low voltage circuit breakers.

32 rows

Nominal InUL / NEC FrameIEC 60947-2 FramePole ResistanceTerminal Torque
15 AMCB 63 AMCB 63 A7.5 mΩ2.5 N·m (22 lb·in)
20 AMCB 63 AMCB 63 A5.0 mΩ2.5 N·m (22 lb·in)
25 AMCB 63 AMCB 63 A3.8 mΩ2.5 N·m (22 lb·in)
30 AMCB 63 AMCB 63 A3.0 mΩ2.5 N·m (22 lb·in)
35 AMCB 63 AMCB 63 A2.5 mΩ2.5 N·m (22 lb·in)
40 AMCB 63 AMCB 63 A2.0 mΩ2.5 N·m (22 lb·in)
45 AMCCB 100 AMCB 63 A1.8 mΩ4.0 N·m (35 lb·in)
50 AMCCB 100 AMCB 63 A1.5 mΩ4.0 N·m (35 lb·in)
60 AMCCB 100 AMCB 63 A1.2 mΩ4.0 N·m (35 lb·in)
70 AMCCB 100 AMCCB 100 A1.0 mΩ5.0 N·m (45 lb·in)
80 AMCCB 100 AMCCB 100 A0.8 mΩ5.0 N·m (45 lb·in)
90 AMCCB 100 AMCCB 100 A0.7 mΩ5.0 N·m (45 lb·in)
100 AMCCB 100 AMCCB 100 A0.6 mΩ5.0 N·m (45 lb·in)
110 AMCCB 150 AMCCB 160 A0.55 mΩ13.5 N·m (120 lb·in)
125 AMCCB 150 AMCCB 160 A0.5 mΩ13.5 N·m (120 lb·in)
150 AMCCB 150 AMCCB 160 A0.4 mΩ13.5 N·m (120 lb·in)
175 AMCCB 250 AMCCB 250 A0.35 mΩ22.5 N·m (200 lb·in)
200 AMCCB 250 AMCCB 250 A0.3 mΩ22.5 N·m (200 lb·in)
225 AMCCB 250 AMCCB 250 A0.27 mΩ22.5 N·m (200 lb·in)
250 AMCCB 250 AMCCB 250 A0.25 mΩ22.5 N·m (200 lb·in)
300 AMCCB 400 AMCCB 400 A0.2 mΩ31.0 N·m (275 lb·in)
350 AMCCB 400 AMCCB 400 A0.17 mΩ31.0 N·m (275 lb·in)
400 AMCCB 400 AMCCB 400 A0.15 mΩ31.0 N·m (275 lb·in)
450 AMCCB 600 AMCCB 630 A0.13 mΩ42.0 N·m (375 lb·in)
500 AMCCB 600 AMCCB 630 A0.12 mΩ42.0 N·m (375 lb·in)
600 AMCCB 600 AMCCB 630 A0.1 mΩ42.0 N·m (375 lb·in)
700 AMCCB 800 AMCCB 800 A0.09 mΩ42.0 N·m (375 lb·in)
800 AMCCB 800 AMCCB 800 A0.08 mΩ42.0 N·m (375 lb·in)
1000 AICCB 1000 AACB 1000 A0.06 mΩ54.0 N·m (480 lb·in)
1200 AICCB 1200 AACB 1200 A0.05 mΩ54.0 N·m (480 lb·in)
1600 AICCB 1600 AACB 1600 A0.04 mΩ54.0 N·m (480 lb·in)
2000 AICCB 2000 AACB 2000 A0.03 mΩ68.0 N·m (600 lb·in)

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Questions

What technical specifications does the breaker parameters table include?

Interruption capacities (Icu, Ics), operating voltage and trip adjustment of low voltage circuit breakers. It compiles 32 reference entries organized across Nominal In, UL / NEC Frame, IEC 60947-2 Frame, Pole Resistance and Terminal Torque for fast lookup during design and field maintenance.

How do you look up and select the right rating in breaker parameters?

Locate the target nominal in in the first column (spanning from 15 A through 2000 A) or type any designation, size, or rating into the search bar above to filter matching rows instantly.

What practical factors should you check when applying breaker parameters data?

Confirm that the protective device clears both sustained overloads and bolted faults within the conductor thermal withstand time while maintaining bonding continuity and upstream selectivity.