Water Heater & Electric Shower

Size the breaker, copper wire gauge (AWG & mm²), and GFCI/RCD protection for electric water heaters, instant showers, and resistive appliances.

W
Phases
—

Enter your values to calculate instantly.

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

Quick breaker & wire size table for electric water heaters and showers

PowerVoltageCurrentBreaker (NEC · IEC)Copper wire (AWG · mm²)
3 500 W127 V27.6 A30 A · 32 A10 AWG · 6 mm²
4 400 W127 V34.6 A40 A · 40 A8 AWG · 10 mm²
4 500 W220 V20.5 A25 A · 25 A10 AWG · 4 mm²
5 500 W127 V43.3 A50 A · 50 A8 AWG · 10 mm²
5 500 W220 V25 A30 A · 32 A10 AWG · 6 mm²
6 500 W220 V29.5 A35 A · 32 A8 AWG · 6 mm²
6 800 W220 V30.9 A35 A · 40 A8 AWG · 10 mm²
7 500 W220 V34.1 A40 A · 40 A8 AWG · 10 mm²
7 800 W220 V35.5 A40 A · 40 A8 AWG · 10 mm²

How it’s calculated

A 5,500 W heater draws 25 A at 220 V (30–32 A breaker, 10 AWG / 4–6 mm² copper) vs 43.3 A at 127 V (50 A breaker, 6 AWG / 10 mm²). Always run a dedicated home-run circuit with equipment grounding and 30 mA GFCI/RCD protection.

I=PV(1Φ),I=P3⋅V(3Φ)I = \dfrac{P}{V} \quad (1\Phi), \qquad I = \dfrac{P}{\sqrt{3}\cdot V} \quad (3\Phi)

Questions

What breaker and wire size for a 5,500 W water heater?

At 220–240 V it draws 23–25 A → 30 A (NEC) or 32 A (IEC) breaker with 10 AWG or 6 mm² copper. At 120–127 V it draws 43–46 A → 50 A breaker with 6 AWG or 10 mm² copper.

What breaker and wire for a 7,500 W 220 V heater?

At 220 V it draws 34.1 A: use a 40 A breaker and 8 AWG (6 mm²) copper for short runs, or 6 AWG (10 mm²) for longer runs or bundled conduit.

Can an electric shower be plugged into a standard wall outlet?

No. Standard outlets are rated 15–20 A and will overheat and melt under 25–45 A loads. Hardwire directly using rated porcelain or lever terminal blocks inside a junction box.