How it’s calculated
A 5,500 W heater draws 25 A at 220 V (30–32 A breaker, 10 AWG / 4–6 mm² copper) vs 43.3 A at 127 V (50 A breaker, 6 AWG / 10 mm²). Always run a dedicated home-run circuit with equipment grounding and 30 mA GFCI/RCD protection.
Questions
What breaker and wire size for a 5,500 W water heater?
At 220–240 V it draws 23–25 A → 30 A (NEC) or 32 A (IEC) breaker with 10 AWG or 6 mm² copper. At 120–127 V it draws 43–46 A → 50 A breaker with 6 AWG or 10 mm² copper.
What breaker and wire for a 7,500 W 220 V heater?
At 220 V it draws 34.1 A: use a 40 A breaker and 8 AWG (6 mm²) copper for short runs, or 6 AWG (10 mm²) for longer runs or bundled conduit.
Can an electric shower be plugged into a standard wall outlet?
No. Standard outlets are rated 15–20 A and will overheat and melt under 25–45 A loads. Hardwire directly using rated porcelain or lever terminal blocks inside a junction box.