Circuit Breaker Sizing

Determine standard breaker rating, magnetic trip curve, and cable coordination for general feeders or AC induction motors.

Application Type
—A

Enter your values to calculate instantly.

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

How it’s calculated

General feeders require IB ≤ In ≤ Iz so the breaker protects the conductor against sustained overload. On motor branches, the magnetic trip rides through locked-rotor inrush while a thermal overload relay protects between 115 % and 125 % of full-load current.

IB≤In≤Iz,I2≤1.45⋅IzI_B \leq I_n \leq I_z, \qquad I_2 \leq 1.45 \cdot I_z

Questions

How do you size a circuit breaker for an electrical load?

Select the next standard breaker rating In that meets or exceeds design current (applying a 1.25× factor for continuous loads lasting 3 hours or more) while remaining at or below the protected conductor’s derated ampacity Iz.

What is the practical difference between Type B, C, and D trip curves?

Thermal behavior is identical, while instantaneous magnetic trip occurs at 3–5×In for Curve B (resistive loads and long runs), 5–10×In for Curve C (commercial lighting and general loads), and 10–20×In for Curve D (transformers and high-inrush motors).

Why do electric motors use separate short-circuit and overload protection?

Direct-on-line starting draws 6 to 8 times full-load current briefly: the breaker or motor-circuit protector rides through starting inrush without nuisance tripping while a thermal overload relay set at 115–125 % protects the windings during running.

What does the coordination rule IB ≤ In ≤ Iz mean?

IB is the load operating current, In is the breaker nominal rating, and Iz is the wire’s allowable ampacity: satisfying IB ≤ In ≤ Iz prevents nuisance trips under normal load while guaranteeing the breaker opens before insulation overheats.