How it’s calculated
General feeders require IB ≤ In ≤ Iz so the breaker protects the conductor against sustained overload. On motor branches, the magnetic trip rides through locked-rotor inrush while a thermal overload relay protects between 115 % and 125 % of full-load current.
Questions
How do you size a circuit breaker for an electrical load?
Select the next standard breaker rating In that meets or exceeds design current (applying a 1.25× factor for continuous loads lasting 3 hours or more) while remaining at or below the protected conductor’s derated ampacity Iz.
What is the practical difference between Type B, C, and D trip curves?
Thermal behavior is identical, while instantaneous magnetic trip occurs at 3–5×In for Curve B (resistive loads and long runs), 5–10×In for Curve C (commercial lighting and general loads), and 10–20×In for Curve D (transformers and high-inrush motors).
Why do electric motors use separate short-circuit and overload protection?
Direct-on-line starting draws 6 to 8 times full-load current briefly: the breaker or motor-circuit protector rides through starting inrush without nuisance tripping while a thermal overload relay set at 115–125 % protects the windings during running.
What does the coordination rule IB ≤ In ≤ Iz mean?
IB is the load operating current, In is the breaker nominal rating, and Iz is the wire’s allowable ampacity: satisfying IB ≤ In ≤ Iz prevents nuisance trips under normal load while guaranteeing the breaker opens before insulation overheats.