IEC Extremely Inverse Curve (Class C)

Trip operating time for Class C curve suited for coordination with fuses and thermal cable limits.

-
t =—

Enter your values to calculate instantly.

t = TMS · [80 / ((I / Is)² - 1)]

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

How it’s calculated

t=TMS⋅[80/((I/Is)2−1)]t = TMS \cdot [80 / ((I / Is)^{2} - 1)]
t
IEC Extremely Inverse Curve · s / ms / µs / min
I
Short-Circuit Fault Current · A / kA / mA / µA
Is
Protection Pickup Setting · A / kA / mA / µA
TMS
Time Multiplier Setting · -

Questions

What is the formula for IEC extremely inverse curve and what does each variable mean?

The governing equation is t = TMS · [80 / ((I / Is)² - 1)], solving for t from I (Short-Circuit fault current, A), Is (protection pickup setting, A) and TMS (time multiplier setting, -). Trip operating time for Class C curve suited for coordination with fuses and thermal cable limits.

Which input and output units can you select for IEC extremely inverse curve?

Every parameter includes metric and imperial unit selectors: I [A, kA, mA, µA]; Is [A, kA, mA, µA]; TMS [-]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output t across s, ms, µs, min, h, d.

When is the IEC extremely inverse curve formula used in electrical engineering?

Confirm that the protective device clears both sustained overloads and bolted faults within the conductor thermal withstand time while maintaining bonding continuity and upstream selectivity.