How it’s calculated
- t
- Maximum Fault Clearing Time for Cable · s / ms / µs / min
- k
- Conductor Constant · -
- S
- Conductor Cross Section · mm² / kcmil / cmil / in²
- Icc
- Short-Circuit Current · A / kA / mA / µA
Questions
What is the formula for maximum fault clearing time for cable and what does each variable mean?
The governing equation is t = (k² · S²) / Icc², solving for t from k (conductor constant, -), S (conductor cross section, mm²) and Icc (Short-Circuit current, A). Maximum permissible fault clearing time to protect cable insulation from thermal destruction.
Which input and output units can you select for maximum fault clearing time for cable?
Every parameter includes metric and imperial unit selectors: k [-]; S [mm², kcmil, cmil, in², cm², m²]; Icc [A, kA, mA, µA]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output t across s, ms, µs, min, h, d.
When is the maximum fault clearing time for cable formula used in electrical engineering?
Confirm that the protective device clears both sustained overloads and bolted faults within the conductor thermal withstand time while maintaining bonding continuity and upstream selectivity.