Skip to main content

Vertical Ground Rod Resistance (Dwight Formula)

Grounding resistance to remote earth of vertical metallic electrode driven into homogeneous soil.

R =—

Enter your values to calculate instantly.

R = [ρ / (2π·L)] · [ln(8L / d) - 1]

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

How it’s calculated

R=[ρ/(2π⋅L)]⋅[ln⁡(8L/d)−1]R = [\rho / (2\pi \cdot L)] \cdot [\ln(8L / d) - 1]
R
Vertical Ground Rod Resistance · Ω / mΩ / kΩ / MΩ
ρ
Soil Resistivity · Ω·m / Ω·cm / Ω·mm²/m / µΩ·cm
L
Ground Rod Length · m / ft / in / yd
d
Ground Rod Diameter · mm / in / cm / m

Questions

What is the formula for vertical ground rod resistance and what does each variable mean?

The governing equation is R = [ρ / (2π·L)] · [ln(8L / d) - 1], solving for R from ρ (soil resistivity, Ω·m), L (ground rod length, m) and d (ground rod diameter, mm). Grounding resistance to remote earth of vertical metallic electrode driven into homogeneous soil.

Which input and output units can you select for vertical ground rod resistance?

Every parameter includes metric and imperial unit selectors: ρ [Ω·m, Ω·cm, Ω·mm²/m, µΩ·cm, Ω·cmil/ft]; L [m, ft, in, yd, mi, km, cm, mm]; d [mm, in, cm, m, mil]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output R across Ω, mΩ, kΩ, MΩ, µΩ.

When is the vertical ground rod resistance formula used in electrical engineering?

Confirm that the protective device clears both sustained overloads and bolted faults within the conductor thermal withstand time while maintaining bonding continuity and upstream selectivity.