TT Earthing System Touch Voltage (Uf)

Electric potential applied across human body touching exposed conductive part under ground fault in TT scheme.

Uf =—

Enter your values to calculate instantly.

Uf = Id · RA = V₀ · (RA / (RA + RB))

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

How it’s calculated

Uf=Id⋅RA=V0⋅(RA/(RA+RB))Uf = Id \cdot RA = V_{0} \cdot (RA / (RA + RB))
Uf
TT Earthing System Touch Voltage · V / kV / mV / µV
V0
Phase-to-Neutral Voltage · V / kV / MV / mV
RA
Exposed Conductive Parts Ground Resistance · Ω / kΩ / MΩ / GΩ
RB
Neutral Grounding Resistance · Ω / kΩ / MΩ / GΩ

Questions

What is the formula for TT earthing system touch voltage and what does each variable mean?

The governing equation is Uf = Id · RA = V₀ · (RA / (RA + RB)), solving for Uf from V0 (Phase-to-Neutral voltage, V), RA (exposed conductive parts ground resistance, Ω) and RB (neutral grounding resistance, Ω). Electric potential applied across human body touching exposed conductive part under ground fault in TT scheme.

Which input and output units can you select for TT earthing system touch voltage?

Every parameter includes metric and imperial unit selectors: V0 [V, kV, MV, mV, µV]; RA [Ω, kΩ, MΩ, GΩ, mΩ, µΩ]; RB [Ω, kΩ, MΩ, GΩ, mΩ, µΩ]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output Uf across V, kV, mV, µV, MV.

When is the TT earthing system touch voltage formula used in electrical engineering?

Confirm that the protective device clears both sustained overloads and bolted faults within the conductor thermal withstand time while maintaining bonding continuity and upstream selectivity.