IEC Standard Inverse Overcurrent Curve (Class A)

Trip operating time for Class A Standard Inverse overcurrent protective relay curve.

-
t =—

Enter your values to calculate instantly.

t = TMS · [0.14 / ((I / Is)^0.02 - 1)]

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

How it’s calculated

t=TMS⋅[0.14/((I/Is)0.02−1)]t = TMS \cdot [0.14 / ((I / Is)^0.02 - 1)]
t
IEC Standard Inverse Overcurrent Curve · s / ms / µs / min
I
Short-Circuit Fault Current · A / kA / mA / µA
Is
Protection Pickup Setting · A / kA / mA / µA
TMS
Time Multiplier Setting · -

Questions

What is the formula for IEC standard inverse overcurrent curve and what does each variable mean?

The governing equation is t = TMS · [0.14 / ((I / Is)^0.02 - 1)], solving for t from I (Short-Circuit fault current, A), Is (protection pickup setting, A) and TMS (time multiplier setting, -). Trip operating time for Class A Standard Inverse overcurrent protective relay curve.

Which input and output units can you select for IEC standard inverse overcurrent curve?

Every parameter includes metric and imperial unit selectors: I [A, kA, mA, µA]; Is [A, kA, mA, µA]; TMS [-]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output t across s, ms, µs, min, h, d.

When is the IEC standard inverse overcurrent curve formula used in electrical engineering?

Confirm that the protective device clears both sustained overloads and bolted faults within the conductor thermal withstand time while maintaining bonding continuity and upstream selectivity.