Insulation Nomenclature

Reference guide to nomenclatures (THHN, THWN, XHHW, etc.) and maximum operating temperatures for commercial insulation.

8 rows

Insulation CodeTemp RatingVoltagePolymer / JacketStandard
THHN / THWN-290 °C / 194 °F (dry & wet)600 VPVC + nylon jacketNEC 310.4(A)
XHHW-290 °C / 194 °F (dry & wet)600 VCross-linked polyethylene (XLPE)NEC 310.4(A)
RHW-2 / USE-290 °C / 194 °F (direct burial)600 V / 2 kVHeavy-duty EPDM / XLPENEC 338 / UL 854
PV Wire / H1Z2Z2-K90 °C (120 °C / 248 °F max)1500 V DCUV-resistant halogen-free XLPEUL 4703 / EN 50618
RZ1-K (AS)90 °C0.6/1 kVXLPE + LSZH polyolefinIEC 60502-1 / UNE 21123
RV-K90 °C0.6/1 kVXLPE + flexible PVC sheathIEC 60502-1
NYY / NYM-J70 °C0.6/1 kVFixed-wiring PVCDIN VDE 0276-603
MI (mineral-insulated)250 °C600 VMagnesium oxide + copper sheathNEC Art. 332

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Questions

What technical specifications does the insulation nomenclature table include?

Reference guide to nomenclatures (THHN, THWN, XHHW, etc.) and maximum operating temperatures for commercial insulation. It compiles 8 reference entries organized across Insulation Code, Temp Rating, Voltage, Polymer / Jacket and Standard for fast lookup during design and field maintenance.

How do you look up and select the right rating in insulation nomenclature?

Locate the target insulation code in the first column (spanning from THHN / THWN-2 through MI (mineral-insulated)) or type any designation, size, or rating into the search bar above to filter matching rows instantly.

What practical factors should you check when applying insulation nomenclature data?

Always verify both thermal ampacity adjusted for ambient temperature and conduit bundling alongside end-of-line voltage drop to prevent insulation overheating and excess energy loss.