Cable Dimensions

Cable diameter and weight reference tables.

12 rows

THHN/THWN-2 SizeOuter DiameterTotal Insulated AreaApprox. Cu Mass40% EMT Fill Ref.
14 AWG (2.08 mm²)2.82 mm6.26 mm²31 kg/km1/2" EMT (max 12)
12 AWG (3.31 mm²)3.30 mm8.58 mm²46 kg/km1/2" EMT (max 9)
10 AWG (5.26 mm²)4.17 mm13.61 mm²73 kg/km1/2" EMT (max 5)
8 AWG (8.37 mm²)5.49 mm23.61 mm²118 kg/km3/4" EMT (max 5)
6 AWG (13.3 mm²)6.45 mm32.71 mm²182 kg/km3/4" EMT (max 4)
4 AWG (21.2 mm²)8.23 mm53.16 mm²285 kg/km1" EMT (max 4)
2 AWG (33.6 mm²)9.75 mm74.71 mm²438 kg/km1-1/4" EMT (max 5)
1/0 AWG (53.5 mm²)12.34 mm119.7 mm²688 kg/km1-1/2" EMT (max 4)
2/0 AWG (67.4 mm²)13.51 mm143.5 mm²858 kg/km2" EMT (max 6)
4/0 AWG (107.2 mm²)16.31 mm208.8 mm²1342 kg/km2" EMT (max 4)
250 kcmil (127 mm²)18.06 mm256.1 mm²1585 kg/km2-1/2" EMT (max 5)
500 kcmil (253 mm²)24.13 mm456.8 mm²3095 kg/km3" EMT (max 5)

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Questions

What technical specifications does the cable dimensions table include?

Cable diameter and weight reference tables. It compiles 12 reference entries organized across THHN/THWN-2 Size, Outer Diameter, Total Insulated Area, Approx. Cu Mass and 40% EMT Fill Ref. for fast lookup during design and field maintenance.

How do you look up and select the right rating in cable dimensions?

Locate the target THHN/THWN-2 size in the first column (spanning from 14 AWG (2.08 mm²) through 500 kcmil (253 mm²)) or type any designation, size, or rating into the search bar above to filter matching rows instantly.

What practical factors should you check when applying cable dimensions data?

Always verify both thermal ampacity adjusted for ambient temperature and conduit bundling alongside end-of-line voltage drop to prevent insulation overheating and excess energy loss.