Medium Voltage Conductors

Design considerations, insulation and semiconductor screens for distribution networks and medium voltage feeders.

8 rows

Voltage ClassInsulation100% Insulation133% InsulationRef. Duct Ampacity
2 kVMV-90 / XLP1.52 mm (60 mil)1.91 mm (75 mil)2 AWG Cu: 155 A
5 kVMV-90 / EPR2.29 mm (90 mil)2.92 mm (115 mil)2 AWG Cu: 165 A
8 kVMV-105 / EPR2.92 mm (115 mil)3.56 mm (140 mil)1/0 AWG Cu: 215 A
15 kVMV-90 / MV-1054.45 mm (175 mil)5.59 mm (220 mil)2/0 AWG Cu: 245 A
25 kVXLPE / TR-XLPE6.60 mm (260 mil)8.13 mm (320 mil)4/0 AWG Cu: 325 A
35 kVEPR / TR-XLPE8.76 mm (345 mil)10.67 mm (420 mil)350 kcmil Cu: 435 A
46 kVSubtransmission XLPE11.30 mm (445 mil)12.70 mm (500 mil)500 kcmil Cu: 530 A
69 kVHigh-voltage XLPE16.51 mm (650 mil)18.29 mm (720 mil)750 kcmil Cu: 655 A

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Questions

What technical specifications does the medium voltage conductors table include?

Design considerations, insulation and semiconductor screens for distribution networks and medium voltage feeders. It compiles 8 reference entries organized across Voltage Class, Insulation, 100% Insulation, 133% Insulation and Ref. Duct Ampacity for fast lookup during design and field maintenance.

How do you look up and select the right rating in medium voltage conductors?

Locate the target voltage class in the first column (spanning from 2 kV through 69 kV) or type any designation, size, or rating into the search bar above to filter matching rows instantly.

What practical factors should you check when applying medium voltage conductors data?

Always verify both thermal ampacity adjusted for ambient temperature and conduit bundling alongside end-of-line voltage drop to prevent insulation overheating and excess energy loss.