Wire Size for Amps (AWG & mm²)

Enter circuit amps and run length to get both AWG and mm² conductor size, verified simultaneously for ampacity and ≤ 3% voltage drop.

A
System
V
Conductor material
Continuous load (≥ 3 h)
—

Enter your values to calculate instantly.

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

Quick wire gauge chart by amps (15 A to 200 A)

Current / BreakerCopper (AWG)Copper (mm²)Aluminum (AWG)Aluminum (mm²)Max load @ 220 V
15 A14 AWG1.5 mm²12 AWG2.5 mm²3.3 kW
20 A12 AWG2.5 mm²10 AWG4 mm²4.4 kW
25 A10 AWG4 mm²10 AWG6 mm²5.5 kW
30 A10 AWG6 mm²8 AWG10 mm²6.6 kW
32 A8 AWG6 mm²8 AWG10 mm²7 kW
40 A8 AWG10 mm²8 AWG16 mm²8.8 kW
50 A8 AWG10 mm²6 AWG16 mm²11 kW
60 A6 AWG16 mm²4 AWG25 mm²13.2 kW
63 A6 AWG16 mm²4 AWG25 mm²13.9 kW
80 A4 AWG25 mm²2 AWG35 mm²17.6 kW
100 A3 AWG35 mm²1 AWG50 mm²22 kW
125 A1 AWG50 mm²2/0 AWG70 mm²27.5 kW
150 A1/0 AWG70 mm²3/0 AWG95 mm²33 kW
200 A3/0 AWG95 mm²250 kcmil AWG150 mm²44 kW

How it’s calculated

Quick copper rule for short runs: 15 A → 14 AWG (1.5 mm²), 20 A → 12 AWG (2.5 mm²), 30 A → 10 AWG (6 mm²), 50 A → 6–8 AWG (10 mm²), 60 A → 6 AWG (16 mm²), 100 A → 3 AWG (35 mm²). For runs over 80–100 ft (25–30 m) or continuous loads (≥ 3 h), upsize one step to stay within 3% voltage drop.

Smin⁡=k⋅L⋅I⋅ρ0.03⋅VS_{\min} = \dfrac{k \cdot L \cdot I \cdot \rho}{0.03 \cdot V}

Questions

What size wire do I need for 30 amps?

Use 10 AWG copper under NEC (or 6 mm² under IEC) for short 30–32 A circuits. If the one-way run exceeds 80–100 ft at 240 V (or 50 ft at 120 V), upsize to 8 AWG / 10 mm².

What size wire do I need for 50 amps?

For 50 A copper at 75 °C in conduit, 8 AWG (50 A) or 6 AWG (55–65 A for NM-B or continuous loads) is standard; in metric IEC use 10 mm² (16 mm² for long runs). In aluminum, use 6 AWG or 16 mm².

What size wire do I need for 100 amps?

A 100 A copper feeder requires 3 AWG (2 AWG on longer runs) under NEC 310.16, or 35 mm² under IEC. Aluminum requires 1 AWG (NEC) or 50 mm² (IEC).

When should I apply the 125% continuous load factor?

Apply 125% whenever the load operates at full current for 3 hours or more continuously (EV chargers, commercial lighting, servers, HVAC compressors, or heaters).