How it’s calculated
Quick copper rule for short runs: 15 A → 14 AWG (1.5 mm²), 20 A → 12 AWG (2.5 mm²), 30 A → 10 AWG (6 mm²), 50 A → 6–8 AWG (10 mm²), 60 A → 6 AWG (16 mm²), 100 A → 3 AWG (35 mm²). For runs over 80–100 ft (25–30 m) or continuous loads (≥ 3 h), upsize one step to stay within 3% voltage drop.
Questions
What size wire do I need for 30 amps?
Use 10 AWG copper under NEC (or 6 mm² under IEC) for short 30–32 A circuits. If the one-way run exceeds 80–100 ft at 240 V (or 50 ft at 120 V), upsize to 8 AWG / 10 mm².
What size wire do I need for 50 amps?
For 50 A copper at 75 °C in conduit, 8 AWG (50 A) or 6 AWG (55–65 A for NM-B or continuous loads) is standard; in metric IEC use 10 mm² (16 mm² for long runs). In aluminum, use 6 AWG or 16 mm².
What size wire do I need for 100 amps?
A 100 A copper feeder requires 3 AWG (2 AWG on longer runs) under NEC 310.16, or 35 mm² under IEC. Aluminum requires 1 AWG (NEC) or 50 mm² (IEC).
When should I apply the 125% continuous load factor?
Apply 125% whenever the load operates at full current for 3 hours or more continuously (EV chargers, commercial lighting, servers, HVAC compressors, or heaters).