Conductor Parameters

Exact equivalences, cross-sectional areas and current capacities between the American AWG standard and the international metric system.

21 rows

AWG / kcmilExact AreaStandard mm²Core DiameterCu R AC 75 °CCu 75 °C (167 °F)
18 AWG0.823 mm²1.0 mm²1.02 mm21.4 Ω/km14 A
16 AWG1.31 mm²1.5 mm²1.29 mm13.2 Ω/km18 A
14 AWG2.08 mm²2.5 mm²1.63 mm10.3 Ω/km20 A
12 AWG3.31 mm²4 mm²2.05 mm6.50 Ω/km25 A
10 AWG5.26 mm²6 mm²2.59 mm4.07 Ω/km35 A
8 AWG8.37 mm²10 mm²3.26 mm2.55 Ω/km50 A
6 AWG13.30 mm²16 mm²4.11 mm1.61 Ω/km65 A
4 AWG21.15 mm²25 mm²5.19 mm1.01 Ω/km85 A
3 AWG26.67 mm²25 mm²5.83 mm0.804 Ω/km100 A
2 AWG33.62 mm²35 mm²6.54 mm0.636 Ω/km115 A
1 AWG42.41 mm²50 mm²7.35 mm0.505 Ω/km130 A
1/0 AWG53.49 mm²50 mm²8.25 mm0.400 Ω/km150 A
2/0 AWG67.43 mm²70 mm²9.27 mm0.317 Ω/km175 A
3/0 AWG85.01 mm²95 mm²10.40 mm0.251 Ω/km200 A
4/0 AWG107.2 mm²120 mm²11.68 mm0.199 Ω/km230 A
250 kcmil126.7 mm²120 mm²12.70 mm0.169 Ω/km255 A
300 kcmil152.0 mm²150 mm²13.91 mm0.141 Ω/km285 A
350 kcmil177.3 mm²185 mm²15.03 mm0.121 Ω/km310 A
500 kcmil253.4 mm²240 mm²17.95 mm0.0845 Ω/km380 A
750 kcmil380.0 mm²400 mm²21.98 mm0.0563 Ω/km475 A
1000 kcmil506.7 mm²500 mm²25.38 mm0.0423 Ω/km545 A

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Questions

What technical specifications does the conductor parameters table include?

Exact equivalences, cross-sectional areas and current capacities between the American AWG standard and the international metric system. It compiles 21 reference entries organized across AWG / kcmil, Exact Area, Standard mm², Core Diameter, Cu R AC 75 °C and Cu 75 °C (167 °F) for fast lookup during design and field maintenance.

How do you look up and select the right rating in conductor parameters?

Locate the target AWG / kcmil in the first column (spanning from 18 AWG through 1000 kcmil) or type any designation, size, or rating into the search bar above to filter matching rows instantly.

What practical factors should you check when applying conductor parameters data?

Always verify both thermal ampacity adjusted for ambient temperature and conduit bundling alongside end-of-line voltage drop to prevent insulation overheating and excess energy loss.