How it’s calculated
Branch-circuit voltage drop is typically kept within 3 % for lighting and sensitive loads, and within 5 % across the combined feeder and branch circuit run.
Questions
How do you calculate voltage drop in both feet (Ω/1000 ft) and meters (Ω/km)?
Single-phase and DC circuits use ΔV = 2 × I × (L / 1000) × (R cos φ + X sin φ), while balanced three-phase circuits replace 2 with √3: pair L in feet with R and X in Ω/1000 ft, or L in meters with R and X in Ω/km (1 Ω/1000 ft = 3.2808 Ω/km). Divide ΔV by nominal voltage times 100 for percentage drop.
What is the maximum recommended voltage drop percentage?
Standard engineering practice limits voltage drop to 3 % on individual lighting or sensitive branch circuits and 5 % total across the combined feeder and branch-circuit run to the farthest load.
Why does inductive reactance X matter in conductors 1/0 AWG (50 mm²) and larger?
In large feeders (≥ 1/0 AWG or 50 mm²), AC resistance drops below 0.12 Ω/1000 ft (0.39 Ω/km) while inductive reactance stays near 0.03–0.045 Ω/1000 ft (0.09–0.14 Ω/km). Ignoring X underestimates actual voltage drop by up to 25 % on inductive loads.
How do you reduce excessive voltage drop on long wire runs?
Step up to the next standard AWG/kcmil gauge or mm² cable size, switch from aluminum to copper, distribute power at a higher system voltage (e.g., three-phase 208/480 V or 230/400 V instead of single-phase), or place the subpanel closer to the load.