How it’s calculated
Derated ampacity must meet or exceed design current while respecting equipment terminal temperature limits (typically 75 °C / 167 °F), even when 90 °C (194 °F) insulation is used as the starting point for derating.
Questions
How do you size a wire in AWG/kcmil or mm² by amperage?
Start from design current (multiplying continuous loads lasting 3 hours or more by 1.25), divide by ambient-temperature and conduit-bundling derating factors, select the next standard size up in AWG/kcmil or mm², and verify voltage drop on long runs.
When should you choose 90 °C (194 °F) insulation over 70/75 °C (158/167 °F) wire?
Thermoset 90 °C (194 °F, THHN/XLPE/EPR) insulation provides 20–25 % higher base ampacity and suffers less derating in hot environments or crowded conduits, provided final current never exceeds the equipment terminal rating (typically 75 °C / 167 °F).
How much larger must aluminum wire be compared to copper for the same current?
Because electrical-grade aluminum has roughly 61 % of copper’s conductivity, aluminum feeders typically step up one to two standard sizes (for example, 4 AWG Al instead of 6 AWG Cu, or 25 mm² Al instead of 16 mm² Cu) with dual-rated Cu/Al lugs.
How do ambient temperatures above 30 °C (86 °F) and bundling affect wire ampacity?
Both restrict dissipation of Joule heat (I²R): temperatures above the 30 °C (86 °F) reference and additional current-carrying conductors sharing a raceway apply multiplicative derating factors below 1.0 to allowable amperage.