Skip to main content

Busbar Parameters

Mechanical and electrical properties, including current capacity and short-circuit resistance, of copper and aluminum bus bars.

20 rows

Busbar (mm / in)Area (mm²)Cu Ampacity 1x / 2x (A)Al Ampacity 1x / 2x (A)Cu R AC (mΩ/m)
12 x 2 mm (1/2" x 5/64")24.0 mm²70 A / 112 A55 A / 88 A0.718 mΩ/m
15 x 2 mm (9/16" x 5/64")30.0 mm²85 A / 136 A65 A / 104 A0.575 mΩ/m
15 x 3 mm (9/16" x 1/8")45.0 mm²110 A / 180 A85 A / 140 A0.384 mΩ/m
20 x 3 mm (3/4" x 1/8")60.0 mm²150 A / 245 A115 A / 190 A0.289 mΩ/m
20 x 5 mm (3/4" x 3/16")100.0 mm²200 A / 320 A155 A / 248 A0.174 mΩ/m
25 x 3 mm (1" x 1/8")75.0 mm²170 A / 272 A130 A / 208 A0.232 mΩ/m
25 x 5 mm (1" x 3/16")125.0 mm²230 A / 380 A180 A / 295 A0.14 mΩ/m
30 x 3 mm (1-3/16" x 1/8")90.0 mm²200 A / 320 A155 A / 248 A0.193 mΩ/m
30 x 5 mm (1-3/16" x 3/16")150.0 mm²275 A / 450 A215 A / 355 A0.117 mΩ/m
40 x 5 mm (1-9/16" x 3/16")200.0 mm²350 A / 580 A275 A / 450 A0.088 mΩ/m
40 x 10 mm (1-9/16" x 3/8")400.0 mm²600 A / 960 A470 A / 752 A0.045 mΩ/m
50 x 5 mm (2" x 3/16")250.0 mm²425 A / 700 A330 A / 545 A0.071 mΩ/m
50 x 10 mm (2" x 3/8")500.0 mm²750 A / 1200 A580 A / 928 A0.037 mΩ/m
60 x 6 mm (2-3/8" x 1/4")360.0 mm²550 A / 900 A430 A / 710 A0.051 mΩ/m
80 x 8 mm (3-1/8" x 5/16")640.0 mm²800 A / 1320 A620 A / 1020 A0.03 mΩ/m
80 x 10 mm (3-1/8" x 3/8")800.0 mm²1000 A / 1600 A780 A / 1248 A0.024 mΩ/m
100 x 10 mm (4" x 3/8")1000.0 mm²1100 A / 1800 A850 A / 1400 A0.02 mΩ/m
120 x 10 mm (4-3/4" x 3/8")1200.0 mm²1300 A / 2150 A1000 A / 1650 A0.017 mΩ/m
160 x 10 mm (6-1/4" x 3/8")1600.0 mm²1650 A / 2640 A1280 A / 2048 A0.013 mΩ/m
200 x 10 mm (7-7/8" x 3/8")2000.0 mm²2000 A / 3200 A1550 A / 2480 A0.011 mΩ/m

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Questions

What technical specifications does the busbar parameters table include?

Mechanical and electrical properties, including current capacity and short-circuit resistance, of copper and aluminum bus bars. It compiles 20 reference entries organized across Busbar (mm / in), Area (mm²), Cu Ampacity 1x / 2x (A), Al Ampacity 1x / 2x (A) and Cu R AC (mΩ/m) for fast lookup during design and field maintenance.

How do you look up and select the right rating in busbar parameters?

Locate the target busbar (mm / in) in the first column (spanning from 12 x 2 mm (1/2" x 5/64") through 200 x 10 mm (7-7/8" x 3/8")) or type any designation, size, or rating into the search bar above to filter matching rows instantly.

What practical factors should you check when applying busbar parameters data?

Always verify both thermal ampacity adjusted for ambient temperature and conduit bundling alongside end-of-line voltage drop to prevent insulation overheating and excess energy loss.