Color Code Guide

Standard identification of phase, neutral, and ground conductors for electrical systems.

8 rows

Standard / SystemPhases L1 / L2 / L3Neutral (N)Ground (PE / EGC)
IEC Harmonized (230/400 V 3Φ)Brown / Black / GrayLight blueGreen-yellow
North America (120/208 V 3Φ)Black / Red / BlueWhiteGreen or bare copper
Industrial 277/480 V 3ΦBrown / Orange / YellowGrayGreen or bare copper
High-leg Delta (120/240 V)Black / Orange (high-leg) / BlueWhiteGreen
Canada (347/600 V 3Φ)Red / Black / BlueWhiteGreen
Brazil (NBR 5410)Black / White / RedLight blueGreen-yellow or green
Direct current (DC)Red (L+) / White or Blue (L−)Blue (mid-wire M)Green-yellow
UK pre-2004 (legacy)Red / Yellow / BlueBlackGreen-yellow

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Questions

What technical specifications does the color code guide table include?

Standard identification of phase, neutral, and ground conductors for electrical systems. It compiles 8 reference entries organized across Standard / System, Phases L1 / L2 / L3, Neutral (N) and Ground (PE / EGC) for fast lookup during design and field maintenance.

How do you look up and select the right rating in color code guide?

Locate the target standard / system in the first column (spanning from IEC Harmonized (230/400 V 3Φ) through UK pre-2004 (legacy)) or type any designation, size, or rating into the search bar above to filter matching rows instantly.

What practical factors should you check when applying color code guide data?

Always verify both thermal ampacity adjusted for ambient temperature and conduit bundling alongside end-of-line voltage drop to prevent insulation overheating and excess energy loss.

Related buying guides