Adiabatic Cable Short-Circuit Cross-Section

Minimum conductor area required to withstand adiabatic fault heating during clearing time t.

-
S =—

Enter your values to calculate instantly.

S = √(Icc² · t) / k

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

How it’s calculated

S=Icc2⋅t/kS = \sqrt{Icc^{2} \cdot t} / k
S
Adiabatic Cable Short-Circuit Cross-Section · mm² / kcmil / cmil / in²
Icc
Short-Circuit Current · A / kA / mA / µA
t
Clearing Time · s / ms / µs / min
k
Conductor Material Constant · -

Questions

What is the formula for adiabatic cable Short-Circuit Cross-Section and what does each variable mean?

The governing equation is S = √(Icc² · t) / k, solving for S from Icc (Short-Circuit current, A), t (clearing time, s) and k (conductor material constant, -). Minimum conductor area required to withstand adiabatic fault heating during clearing time t.

Which input and output units can you select for adiabatic cable Short-Circuit Cross-Section?

Every parameter includes metric and imperial unit selectors: Icc [A, kA, mA, µA]; t [s, ms, µs, min, h, d]; k [-]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output S across mm², kcmil, cmil, in², cm².

When is the adiabatic cable Short-Circuit Cross-Section formula used in electrical engineering?

Confirm that the protective device clears both sustained overloads and bolted faults within the conductor thermal withstand time while maintaining bonding continuity and upstream selectivity.