Tolerable Touch Voltage (Etouch)

Maximum safe contact potential for a 50 kg person in substation covered with crushed rock surface.

-
Etouch =—

Enter your values to calculate instantly.

Etouch = (1000 + 1.5 · Cs · ρs) · (0.116 / √ts)

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

How it’s calculated

Etouch=(1000+1.5⋅Cs⋅ρs)⋅(0.116/ts)Etouch = (1000 + 1.5 \cdot Cs \cdot \rho s) \cdot (0.116 / \sqrt{ts})
Etouch
Tolerable Touch Voltage · V / kV / mV / µV
ρs
Surface Layer Resistivity · Ω·m / Ω·cm / Ω·mm²/m / µΩ·cm
Cs
Surface Layer Derating Factor · -
ts
Fault Duration · s / ms / µs / min

Questions

What is the formula for tolerable touch voltage and what does each variable mean?

The governing equation is Etouch = (1000 + 1.5 · Cs · ρs) · (0.116 / √ts), solving for Etouch from ρs (surface layer resistivity, Ω·m), Cs (surface layer derating factor, -) and ts (fault duration, s). Maximum safe contact potential for a 50 kg person in substation covered with crushed rock surface.

Which input and output units can you select for tolerable touch voltage?

Every parameter includes metric and imperial unit selectors: ρs [Ω·m, Ω·cm, Ω·mm²/m, µΩ·cm, Ω·cmil/ft]; Cs [-]; ts [s, ms, µs, min, h, d]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output Etouch across V, kV, mV, µV, MV.

When is the tolerable touch voltage formula used in electrical engineering?

Confirm that the protective device clears both sustained overloads and bolted faults within the conductor thermal withstand time while maintaining bonding continuity and upstream selectivity.