| D-11 | Delta (Primary) / Wye with Grounded Neutral (Secondary) | 30° lag (Secondary lags Primary by 30° - 11 o'clock position) | Primary has no neutral. Secondary neutral is available for system grounding and single-phase load connection. |
| YN-11 | Wye with Grounded Neutral (Primary) / Delta (Secondary) | 30° lag (Secondary lags Primary by 30° - 11 o'clock position) | Primary neutral accessible (usually solidly grounded). Secondary neutral not available. |
| Yy0 | Wye (Primary) / Wye (Secondary) - Zero Phase Shift | 0° (Secondary voltages are in phase with primary - 12 o'clock position) | Neutral optionally available on both primary and secondary sides for grounding. |
| Dd0 | Delta (Primary) / Delta (Secondary) - Zero Phase Shift | 0° (Secondary voltages are in phase with primary - 12 o'clock position) | No neutral connection available on either side. |
| D-5 | Delta (Primary) / Wye with Grounded Neutral (Secondary) | 150° lag (Secondary lags Primary by 150° - 5 o'clock position) | Primary has no neutral. Secondary neutral is available for system grounding and single-phase load connection. |
| Yz5 | Wye (Primary) / Zigzag with Grounded Neutral (Secondary) | 150° lag (Secondary lags Primary by 150° - 5 o'clock position) | Primary neutral typically unused. Secondary neutral fully available for heavy single-phase unbalanced loading. |
| Yd11 | Wye (Primary) / Delta (Secondary) | 30° lag (Secondary lags Primary by 30° - 11 o'clock position) | Primary neutral available for system grounding. Secondary neutral not available. |
| Dd6 | Delta (Primary) / Delta (Secondary) - 180° Phase Shift | 180° (Secondary voltages are in opposite phase to primary - 6 o'clock position) | No neutral connection available on either side. |
| YZ-N5 | Wye (Primary) / Zigzag with Grounded Neutral (Secondary) | 150° lag (Secondary lags Primary by 150° - 5 o'clock position) | Primary neutral typically unused. Secondary neutral fully available for grounding and unbalanced loads. |
| D-1 | Delta (Primary) / Wye with Grounded Neutral (Secondary) | 30° lead (Secondary leads Primary by 30° - 1 o'clock position) | Primary has no neutral. Secondary neutral is available for system grounding and single-phase loads. |
| Yy6 | Wye (Primary) / Wye (Secondary) - 180° Phase Shift | 180° (Secondary voltages are in opposite phase to primary - 6 o'clock position) | Neutral optionally available on both sides for grounding. |
| Dz0 | Delta (Primary) / Zigzag with Grounded Neutral (Secondary) - Zero Phase Shift | 0° (Secondary voltages are in phase with primary - 12 o'clock position) | Primary has no neutral. Secondary neutral fully available for grounding and heavy single-phase unbalance. |