Vector Connection Groups

Connection diagrams, phase displacement, and harmonic behavior.

12 rows

Vector GroupHV / LV WindingPhase ShiftNeutral & Harmonic Behavior
D-11Delta (Primary) / Wye with Grounded Neutral (Secondary)30° lag (Secondary lags Primary by 30° - 11 o'clock position)Primary has no neutral. Secondary neutral is available for system grounding and single-phase load connection.
YN-11Wye with Grounded Neutral (Primary) / Delta (Secondary)30° lag (Secondary lags Primary by 30° - 11 o'clock position)Primary neutral accessible (usually solidly grounded). Secondary neutral not available.
Yy0Wye (Primary) / Wye (Secondary) - Zero Phase Shift0° (Secondary voltages are in phase with primary - 12 o'clock position)Neutral optionally available on both primary and secondary sides for grounding.
Dd0Delta (Primary) / Delta (Secondary) - Zero Phase Shift0° (Secondary voltages are in phase with primary - 12 o'clock position)No neutral connection available on either side.
D-5Delta (Primary) / Wye with Grounded Neutral (Secondary)150° lag (Secondary lags Primary by 150° - 5 o'clock position)Primary has no neutral. Secondary neutral is available for system grounding and single-phase load connection.
Yz5Wye (Primary) / Zigzag with Grounded Neutral (Secondary)150° lag (Secondary lags Primary by 150° - 5 o'clock position)Primary neutral typically unused. Secondary neutral fully available for heavy single-phase unbalanced loading.
Yd11Wye (Primary) / Delta (Secondary)30° lag (Secondary lags Primary by 30° - 11 o'clock position)Primary neutral available for system grounding. Secondary neutral not available.
Dd6Delta (Primary) / Delta (Secondary) - 180° Phase Shift180° (Secondary voltages are in opposite phase to primary - 6 o'clock position)No neutral connection available on either side.
YZ-N5Wye (Primary) / Zigzag with Grounded Neutral (Secondary)150° lag (Secondary lags Primary by 150° - 5 o'clock position)Primary neutral typically unused. Secondary neutral fully available for grounding and unbalanced loads.
D-1Delta (Primary) / Wye with Grounded Neutral (Secondary)30° lead (Secondary leads Primary by 30° - 1 o'clock position)Primary has no neutral. Secondary neutral is available for system grounding and single-phase loads.
Yy6Wye (Primary) / Wye (Secondary) - 180° Phase Shift180° (Secondary voltages are in opposite phase to primary - 6 o'clock position)Neutral optionally available on both sides for grounding.
Dz0Delta (Primary) / Zigzag with Grounded Neutral (Secondary) - Zero Phase Shift0° (Secondary voltages are in phase with primary - 12 o'clock position)Primary has no neutral. Secondary neutral fully available for grounding and heavy single-phase unbalance.

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Questions

What technical specifications does the vector connection groups table include?

Connection diagrams, phase displacement, and harmonic behavior. It compiles 12 reference entries organized across Vector Group, HV / LV Winding, Phase Shift and Neutral & Harmonic Behavior for fast lookup during design and field maintenance.

How do you look up and select the right rating in vector connection groups?

Locate the target vector group in the first column (spanning from D-11 through Dz0) or type any designation, size, or rating into the search bar above to filter matching rows instantly.

What practical factors should you check when applying vector connection groups data?

Evaluate total apparent power in kVA, future expansion headroom, secondary voltage regulation under load, and prospective fault current set by the transformer percent impedance.