Cooling Methods

ONAN, ONAF, OFAF, and AN/AF cooling designations for liquid-immersed and dry-type transformers.

13 rows

IEC CodeIEEE CodeDesignationTypical Rating
ONANOAOil Natural / Air NaturalTypically up to 5 MVA (Small and medium distribution transformers)
ONAFFAOil Natural / Air ForcedTypically between 5 MVA and 15 MVA (Medium substation transformers)
OFAFFOAOil Forced / Air ForcedTypically above 15 MVA (Large transmission and substation power transformers)
OFANFOWOil Forced / Water NaturalTypically above 20 MVA (Hydroelectric generation plants or heavy facilities with abundant water supply)
ODAFFOA-DOil Directed / Air ForcedTypically above 50 MVA (Large power transformers in EHV generation and transmission substations)
ANAAAir Natural (Dry-Type)Typically up to 3 MVA (Indoor installations, building substations, shopping malls)
AFAFAAir Forced (Dry-Type)Typically up to 5 MVA (Designed to handle temporary overloads in dry-type systems)
OFWFFOWOil Forced / Water ForcedTypically above 30 MVA (Large generator systems and smelting furnaces)
ODWFFOW-DOil Directed / Water ForcedTypically above 100 MVA (Ultra-high capacity generator transformers and main transmission grid ties)
KNANK-OANatural Ester / Air NaturalTypically up to 10 MVA (Ecologically sensitive zones, wind farms, and urban distribution)
KNAFK-FANatural Ester / Air ForcedTypically between 10 MVA and 30 MVA (Urban substations and renewable generation plants)
LNANL-OASilicone Natural / Air NaturalTypically up to 5 MVA (High-rise buildings, offshore platforms, transit subways, and high fire risk areas)
ANAFAA/FAAir Natural / Air Forced (Dry-Type)Typically up to 5 MVA (Systems experiencing cyclic industrial peaks or seasonal overload patterns)

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Questions

What technical specifications does the cooling methods table include?

ONAN, ONAF, OFAF, and AN/AF cooling designations for liquid-immersed and dry-type transformers. It compiles 13 reference entries organized across IEC Code, IEEE Code, Designation and Typical Rating for fast lookup during design and field maintenance.

How do you look up and select the right rating in cooling methods?

Locate the target IEC code in the first column (spanning from ONAN through ANAF) or type any designation, size, or rating into the search bar above to filter matching rows instantly.

What practical factors should you check when applying cooling methods data?

Evaluate total apparent power in kVA, future expansion headroom, secondary voltage regulation under load, and prospective fault current set by the transformer percent impedance.

Related buying guides