How it’s calculated
Every protective breaker must have an interrupting rating (AIC or Icu) exceeding the prospective symmetrical fault current at its point of installation to clear bolted faults safely.
Questions
How do you calculate transformer secondary short-circuit current?
First find nominal full-load current In = (kVA × 1000) / (√3 × V), then divide by per-unit impedance (%Z / 100) plus upstream utility grid per-unit impedance to obtain three-phase symmetrical fault current in kA.
Why can replacing a transformer with a lower-impedance unit (%Z < 4 %) create a switchgear hazard?
Available fault current is inversely proportional to %Z: dropping impedance from 6 % to 4 % increases bolted fault current by 50 %, potentially exceeding existing 10 kA or 22 kA breaker ratings.
What is the difference between symmetrical fault current Ik and peak current ip?
Ik is the RMS value used to select breaker interrupting capacity, whereas ip is the first-half-cycle asymmetrical peak current that governs mechanical electrodynamic forces on busbars and supports.
Why check adiabatic conductor sizing against fault clearing time?
During a bolted fault, heat cannot escape to the surroundings: evaluating S = (Ik × √t) / k verifies that let-through energy I²t will not melt cable insulation before the breaker clears.