| A | Dry-Type Transformer | 55°C (over nominal ambient temperature of 30°C average / 40°C max) | 105°C (Absolute maximum limit at the winding hot-spot) |
| B | Dry-Type Transformer | 80°C (over nominal ambient temperature of 30°C average / 40°C max) | 130°C (Absolute maximum limit at the winding hot-spot) |
| F | Dry-Type Transformer | 115°C (over nominal ambient temperature of 30°C average / 40°C max) | 155°C (Absolute maximum limit at the winding hot-spot) |
| H | Dry-Type Transformer | 150°C (over nominal ambient temperature of 30°C average / 40°C max) | 180°C (Absolute maximum limit at the winding hot-spot) |
| R | Dry-Type Transformer | 150°C to 180°C (over nominal ambient temperature of 30°C average / 40°C max) | 220°C (Absolute maximum limit at the winding hot-spot) |
| C | Dry-Type Transformer | 150°C or higher (typically up to 180°C or 220°C rise depending on design) | 220°C or higher (Absolute maximum limit for ultra-high temperature systems, often without defined limit) |
| 55°C | Liquid-Immersed Transformer | 55°C (over nominal ambient temperature of 30°C average / 40°C max) | 95°C (Maximum winding hot-spot limit to prevent accelerated paper degradation) |
| 65°C | Liquid-Immersed Transformer | 65°C (over nominal ambient temperature of 30°C average / 40°C max) | 110°C (Maximum winding hot-spot limit thanks to thermally upgraded Kraft paper) |
| 75°C | Liquid-Immersed Transformer | 75°C (over nominal ambient temperature of 30°C average / 40°C max) | 120°C to 130°C (Winding hot-spot limit enabled by natural/synthetic ester fluids and upgraded Nomex/TUP insulation) |
| 55/65°C | Liquid-Immersed Transformer | 55°C under passive cooling (ONAN) / 65°C with active fan cooling (ONAF) | 95°C during base 55°C rating / 110°C during increased 65°C rating |
| E | Dry-Type Transformer | 75°C (over nominal ambient temperature of 30°C average / 40°C max) | 120°C (Absolute maximum limit at the winding hot-spot) |
| 85°C | Liquid-Immersed Transformer | 85°C (over nominal ambient temperature of 30°C average / 40°C max) | 130°C to 140°C (Winding hot-spot limit using high fire point fluids and solid hybrid insulation) |
| 115°C | Liquid-Immersed Transformer | 115°C (over nominal ambient temperature of 30°C average / 40°C max) | 160°C to 180°C (Winding hot-spot limit using 100% solid aramid insulation and synthetic esters or silicone fluids) |