How it’s calculated
- IN
- Unbalanced Neutral Current · A / kA / mA / µA
- Ia
- Phase A Current · A / kA / mA / µA
- Ib
- Phase B Current · A / kA / mA / µA
- Ic
- Phase C Current · A / kA / mA / µA
Questions
What is the formula for unbalanced neutral current and what does each variable mean?
The governing equation is IN = √(Ia² + Ib² + Ic² - Ia·Ib - Ib·Ic - Ic·Ia), solving for IN from Ia (phase A current, A), Ib (phase B current, A) and Ic (phase C current, A). Calculates neutral current in a 4-wire unbalanced system.
Which input and output units can you select for unbalanced neutral current?
Every parameter includes metric and imperial unit selectors: Ia [A, kA, mA, µA]; Ib [A, kA, mA, µA]; Ic [A, kA, mA, µA]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output IN across A, kA, mA, µA.
When is the unbalanced neutral current formula used in electrical engineering?
Work with True RMS measurements, distinguish active (kW), apparent (kVA), and reactive (kVAR) power, and check harmonic distortion before switching capacitor banks onto the bus.