How it’s calculated
Motor nameplates state mechanical shaft output power (HP or kW), not electrical input power: divide shaft output by motor efficiency η as well as power factor cosφ to find line current.
Questions
How do you convert between kW, kVA, and amps both ways in a three-phase system?
From kW to amps: I = (kW × 1000) / (√3 × V × cos φ), and from kVA: I = (kVA × 1000) / (√3 × V). Going the opposite way from measured line current, S (kVA) = (√3 × V × I) / 1000 and P (kW) = (√3 × V × I × cos φ) / 1000.
What is the difference between kW, kVA, and kVAR?
kW is active power that performs real mechanical work or heating, kVAR is reactive power that magnetizes motor and transformer windings, and kVA is vector apparent power (S = √(P² + Q²)) that dictates wire and transformer current.
Why are transformers and generators rated in kVA instead of kW?
Core losses depend on voltage (V) while winding copper losses depend on total current (A), regardless of the connected load’s power factor cosφ.
Why must motor efficiency η be included when converting HP to amps?
Because nameplate HP or kW indicates mechanical output at the shaft; the electrical supply must deliver shaft power divided by efficiency η (typically 85–95 %) as well as power factor cos φ.