kVA to Amps & kW

Convert apparent power (kVA) to line current (A), real power (kW), and reactive power (kVAR) for transformers, generators, and switchgear.

Conversion
System
kVA
V
—

Enter your values to calculate instantly.

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

Three-phase kVA to amps & kW quick reference chart (5 kVA to 2500 kVA)

Power (kVA)kW (PF 0.8)3Φ 208 V3Φ 220 V3Φ 400 V3Φ 480 V
5 kVA4 kW13.9 A13.1 A7.2 A6 A
10 kVA8 kW27.8 A26.2 A14.4 A12 A
15 kVA12 kW41.6 A39.4 A21.7 A18 A
25 kVA20 kW69.4 A65.6 A36.1 A30.1 A
30 kVA24 kW83.3 A78.7 A43.3 A36.1 A
45 kVA36 kW124.9 A118.1 A65 A54.1 A
50 kVA40 kW138.8 A131.2 A72.2 A60.1 A
75 kVA60 kW208.2 A196.8 A108.3 A90.2 A
100 kVA80 kW277.6 A262.4 A144.3 A120.3 A
150 kVA120 kW416.4 A393.6 A216.5 A180.4 A
225 kVA180 kW624.5 A590.5 A324.8 A270.6 A
300 kVA240 kW832.7 A787.3 A433 A360.8 A
500 kVA400 kW1 387.9 A1 312.2 A721.7 A601.4 A
750 kVA600 kW2 081.8 A1 968.2 A1 082.5 A902.1 A
1 000 kVA800 kW2 775.7 A2 624.3 A1 443.4 A1 202.8 A
1 500 kVA1 200 kW4 163.6 A3 936.5 A2 165.1 A1 804.2 A
2 500 kVA2 000 kW6 939.3 A6 560.8 A3 608.4 A3 007 A

How it’s calculated

For three-phase systems, I (A) = kVA × 1000 ÷ (√3 × V). Fast multipliers: at 480 V multiply kVA by 1.20 A/kVA; at 400 V by 1.44 A/kVA; at 208 V by 2.78 A/kVA. To convert kVA to kW, multiply by power factor (typically 0.8 for generators).

I=kVA×10003⋅V,kW=kVA⋅cos⁡φI = \dfrac{\text{kVA} \times 1000}{\sqrt{3} \cdot V}, \qquad \text{kW} = \text{kVA} \cdot \cos\varphi
Three-phase (3Φ)
I=kVA×1000V,kVAR=kVA⋅1−cos⁡2φI = \dfrac{\text{kVA} \times 1000}{V}, \qquad \text{kVAR} = \text{kVA} \cdot \sqrt{1 - \cos^2\varphi}
Single-phase (1Φ)

Questions

How many amps is 100 kVA three-phase?

A 100 kVA 3-phase transformer or generator delivers 277.6 A at 208 V, 262.4 A at 220 V, 144.3 A at 400 V, and 120.3 A at 480 V. At 0.8 PF it delivers 80 kW.

What is the difference between kVA and kW?

kVA is total apparent power carried by cables and transformers, while kW is real working power. They are linked by power factor: kW = kVA × PF.