How it’s calculated
Raising plant power factor from 0.72 to 0.96 cuts feeder line current by 25 % and reduces conductor I²R heating losses by nearly 44 %, freeing up transformer capacity.
Questions
How do you calculate the kVAR needed for power factor correction?
Multiply active power P in kW by the difference of phase-angle tangents: Qc = P × [tan(arccos cos φ1) − tan(arccos cos φ2)]. The result gives the exact capacitive reactive power in kVAR.
What target power factor is recommended for industrial plants?
Targeting 0.95 to 0.97 lagging eliminates utility reactive penalties and frees transformer kVA while avoiding unity (1.00), preventing leading capacitive overvoltage when plant loads cycle off.
When do capacitor banks require detuned harmonic filter reactors (7 % or 14 %)?
Whenever non-linear loads (VFDs, UPS systems, rectifiers) exceed 15–20 % of transformer kVA or current THD exceeds 15 %, detuned reactors prevent parallel harmonic resonance with the supply transformer.
How much transformer kVA capacity does power factor correction free up?
Apparent demand drops from S1 = P / cos φ1 to S2 = P / cos φ2: on a 200 kW load, raising cos φ from 0.75 to 0.96 cuts demand from 266.7 kVA to 208.3 kVA, unlocking 58.4 kVA and reducing feeder I²R losses by 39 %.


