Three-Phase PF Correction Capacitor Bank

Total three-phase kvar rating required to improve power factor from φ1 to target φ2.

Qc =—

Enter your values to calculate instantly.

Qc = P · (tanφ1 - tanφ2)

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

How it’s calculated

Qc=P⋅(tanφ1−tanφ2)Qc = P \cdot (tan\varphi 1 - tan\varphi 2)
Qc
Three-Phase PF Correction Capacitor Bank · VAr / kVAR / MVAR
P
Active Power · W / kW / MW / GW
φ₁
Initial Angle · ° / rad / mrad
φ₂
Target Angle · ° / rad / mrad

Questions

What is the formula for Three-Phase PF correction capacitor bank and what does each variable mean?

The governing equation is Qc = P · (tanφ1 - tanφ2), solving for Qc from P (active power, W), φ₁ (initial angle, °) and φ₂ (target angle, °). Total three-phase kvar rating required to improve power factor from φ1 to target φ2.

Which input and output units can you select for Three-Phase PF correction capacitor bank?

Every parameter includes metric and imperial unit selectors: P [W, kW, MW, GW, HP, CV, BTU/h, TR]; φ₁ [°, rad, mrad]; φ₂ [°, rad, mrad]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output Qc across VAr, kVAR, MVAR.

When is the Three-Phase PF correction capacitor bank formula used in electrical engineering?

Work with True RMS measurements, distinguish active (kW), apparent (kVA), and reactive (kVAR) power, and check harmonic distortion before switching capacitor banks onto the bus.