How it’s calculated
- Icc₂LG
- Double Line-to-Ground Fault · A / kA / mA / µA
- Vph
- Phase-to-Neutral Voltage · V / kV / MV / mV
- Z1
- Positive Sequence Impedance · Ω / kΩ / MΩ / GΩ
- Z2
- Negative Sequence Impedance · Ω / kΩ / MΩ / GΩ
- Z0
- Zero Sequence Impedance · Ω / kΩ / MΩ / GΩ
Questions
What is the formula for double Line-to-Ground fault and what does each variable mean?
The governing equation is Icc₂LG = 3 · Vph · Z₂ / (Z₁·Z₂ + Z₁·Z₀ + Z₂·Z₀), solving for Icc₂LG from Vph (Phase-to-Neutral voltage, V), Z1 (positive sequence impedance, Ω), Z2 (negative sequence impedance, Ω) and Z0 (zero sequence impedance, Ω). Total fault current for a simultaneous two-phase to ground fault via symmetrical components.
Which input and output units can you select for double Line-to-Ground fault?
Every parameter includes metric and imperial unit selectors: Vph [V, kV, MV, mV, µV]; Z1 [Ω, kΩ, MΩ, GΩ, mΩ, µΩ]; Z2 [Ω, kΩ, MΩ, GΩ, mΩ, µΩ]; Z0 [Ω, kΩ, MΩ, GΩ, mΩ, µΩ]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output Icc₂LG across A, kA, mA, µA.
When is the double Line-to-Ground fault formula used in electrical engineering?
Work with True RMS measurements, distinguish active (kW), apparent (kVA), and reactive (kVAR) power, and check harmonic distortion before switching capacitor banks onto the bus.