Phase Angle Power Factor Correction Capacitor (1φ)

Calculates required capacitance from initial phase angle φ1 and target phase angle φ2 in single-phase systems.

C =—

Enter your values to calculate instantly.

C = P·(tanφ1 - tanφ2) / (2π·f·V²)

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

How it’s calculated

C=P⋅(tanφ1−tanφ2)/(2π⋅f⋅V2)C = P \cdot (tan\varphi 1 - tan\varphi 2) / (2\pi \cdot f \cdot V^{2})
C
Phase Angle Power Factor Correction Capacitor · µF / F / mF / nF
P
Active Power · W / kW / MW / GW
φ₁
Initial Angle · ° / rad / mrad
φ₂
Target Angle · ° / rad / mrad
f
Frequency · Hz / kHz / MHz / GHz
V
Mains Voltage · V / kV / MV / mV

Questions

What is the formula for phase angle power factor correction capacitor and what does each variable mean?

The governing equation is C = P·(tanφ1 - tanφ2) / (2π·f·V²), solving for C from P (active power, W), φ₁ (initial angle, °), φ₂ (target angle, °), f (frequency, Hz) and V (mains voltage, V). Calculates required capacitance from initial phase angle φ1 and target phase angle φ2 in single-phase systems.

Which input and output units can you select for phase angle power factor correction capacitor?

Every parameter includes metric and imperial unit selectors: P [W, kW, MW, GW, HP, CV, BTU/h, TR]; φ₁ [°, rad, mrad]; φ₂ [°, rad, mrad]; f [Hz, kHz, MHz, GHz]; V [V, kV, MV, mV, µV]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output C across µF, F, mF, nF, pF.

When is the phase angle power factor correction capacitor formula used in electrical engineering?

Work with True RMS measurements, distinguish active (kW), apparent (kVA), and reactive (kVAR) power, and check harmonic distortion before switching capacitor banks onto the bus.

Related buying guides