How it’s calculated
- PFtrue
- True Power Factor with THDv & THDi
- cos φ₁
- Displacement Power Factor · -
- THDi
- Total Harmonic Current Distortion · % / ratio
- THDv
- Voltage Total Harmonic Distortion · % / ratio
Questions
What is the formula for true power factor with THDv & THDi and what does each variable mean?
The governing equation is PFtrue = DPF / (√(1 + THDi²) · √(1 + THDv²)), solving for PFtrue from cos φ₁ (displacement power factor, -), THDi (total harmonic current distortion, %) and THDv (voltage total harmonic distortion, %). Calculates complete true power factor combining displacement power factor (DPF) and both voltage and current harmonic distortion.
Which input and output units can you select for true power factor with THDv & THDi?
Every parameter includes metric and imperial unit selectors: cos φ₁ [-]; THDi [%, ratio]; THDv [%, ratio]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output PFtrue across SI.
When is the true power factor with THDv & THDi formula used in electrical engineering?
Work with True RMS measurements, distinguish active (kW), apparent (kVA), and reactive (kVAR) power, and check harmonic distortion before switching capacitor banks onto the bus.