Skip to main content

Budeanu Distortion Power (D)

Non-active power component generated by harmonics in non-sinusoidal AC circuits.

D =—

Enter your values to calculate instantly.

D = √(S² - P² - Q²)

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

How it’s calculated

D=S2−P2−Q2D = \sqrt{S^{2} - P^{2} - Q^{2}}
D
Budeanu Distortion Power · VAD / kVAD / MVAD
S
Apparent Power · kVA / VA / MVA / GVA
P
Active Power · kW / W / MW / GW
Q
Fundamental Reactive Power · kVAR / VAR / MVAR

Questions

What is the formula for budeanu distortion power and what does each variable mean?

The governing equation is D = √(S² - P² - Q²), solving for D from S (apparent power, kVA), P (active power, kW) and Q (fundamental reactive power, kVAR). Non-active power component generated by harmonics in non-sinusoidal AC circuits.

Which input and output units can you select for budeanu distortion power?

Every parameter includes metric and imperial unit selectors: S [kVA, VA, MVA, GVA]; P [kW, W, MW, GW, HP, CV, BTU/h, TR]; Q [kVAR, VAR, MVAR]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output D across VAD, kVAD, MVAD.

When is the budeanu distortion power formula used in electrical engineering?

Work with True RMS measurements, distinguish active (kW), apparent (kVA), and reactive (kVAR) power, and check harmonic distortion before switching capacitor banks onto the bus.

Related buying guides