How it’s calculated
- Isc
- Transformer Terminal Short-Circuit Current · kA / A / mA / µA
- Sn
- Rated Power · VA / kVA / MVA / GVA
- Vsec
- Secondary Voltage · V / kV / MV / mV
- %Zcc
- Impedance %Zcc · % / ratio
Questions
What is the formula for transformer terminal Short-Circuit current and what does each variable mean?
The governing equation is Isc = Sn / (√3 · Vsec · (%Z / 100)), solving for Isc from Sn (rated power, VA), Vsec (secondary voltage, V) and %Zcc (impedance %Zcc, %). Maximum prospective symmetrical short-circuit current at secondary terminals in kA.
Which input and output units can you select for transformer terminal Short-Circuit current?
Every parameter includes metric and imperial unit selectors: Sn [VA, kVA, MVA, GVA]; Vsec [V, kV, MV, mV, µV]; %Zcc [%, ratio]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output Isc across kA, A, mA, µA.
When is the transformer terminal Short-Circuit current formula used in electrical engineering?
Evaluate total apparent power in kVA, future expansion headroom, secondary voltage regulation under load, and prospective fault current set by the transformer percent impedance.