Power Factor Correction Capacitor (C)

Calculates the capacitance needed to raise the displacement power factor to a desired target value.

-
-
C =—

Enter your values to calculate instantly.

C = P · (tan(θ₁) - tan(θ₂)) / (2 · π · f · V²)

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

How it’s calculated

C=P⋅(tan⁡(θ1)−tan⁡(θ2))/(2⋅π⋅f⋅V2)C = P \cdot (\tan(\theta _{1}) - \tan(\theta _{2})) / (2 \cdot \pi \cdot f \cdot V^{2})
C
Power Factor Correction Capacitor · µF / F / mF / nF
P
Active Power · W / kW / MW / GW
V
Mains Voltage · V / kV / MV / mV
f
Frequency · Hz / kHz / MHz / GHz
cos φ₁
Current Power Factor · -
cos φ₂
Target Power Factor · -

Questions

What is the formula for power factor correction capacitor and what does each variable mean?

The governing equation is C = P · (tan(θ₁) - tan(θ₂)) / (2 · π · f · V²), solving for C from P (active power, W), V (mains voltage, V), f (frequency, Hz), cos φ₁ (current power factor, -) and cos φ₂ (target power factor, -). Calculates the capacitance needed to raise the displacement power factor to a desired target value.

Which input and output units can you select for power factor correction capacitor?

Every parameter includes metric and imperial unit selectors: P [W, kW, MW, GW, HP, CV, BTU/h, TR]; V [V, kV, MV, mV, µV]; f [Hz, kHz, MHz, GHz]; cos φ₁ [-]; cos φ₂ [-]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output C across µF, F, mF, nF, pF.

When is the power factor correction capacitor formula used in electrical engineering?

Work with True RMS measurements, distinguish active (kW), apparent (kVA), and reactive (kVAR) power, and check harmonic distortion before switching capacitor banks onto the bus.