How it’s calculated
- hr
- Harmonic Resonance Order · order
- Scc
- Short-Circuit Power · MVA / kVA / VA / GVA
- Qc
- Capacitor Bank Power · MVAR / kVAR / VAR
Questions
What is the formula for harmonic resonance order and what does each variable mean?
The governing equation is hr = √(Scc / Qc), solving for hr from Scc (Short-Circuit power, MVA) and Qc (capacitor bank power, MVAR). Calculates the harmonic order at which parallel resonance occurs.
Which input and output units can you select for harmonic resonance order?
Every parameter includes metric and imperial unit selectors: Scc [MVA, kVA, VA, GVA]; Qc [MVAR, kVAR, VAR]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output hr across order.
When is the harmonic resonance order formula used in electrical engineering?
Work with True RMS measurements, distinguish active (kW), apparent (kVA), and reactive (kVAR) power, and check harmonic distortion before switching capacitor banks onto the bus.