Dimensions des Câbles

Tableaux de référence des diamètres et poids des câbles.

12 lignes

Section THHN/THWN-2Diamètre Ext.Section TotaleMasse CuivreRemplissage EMT 40%
14 AWG (2.08 mm²)2.82 mm6.26 mm²31 kg/km1/2" EMT (max 12)
12 AWG (3.31 mm²)3.30 mm8.58 mm²46 kg/km1/2" EMT (max 9)
10 AWG (5.26 mm²)4.17 mm13.61 mm²73 kg/km1/2" EMT (max 5)
8 AWG (8.37 mm²)5.49 mm23.61 mm²118 kg/km3/4" EMT (max 5)
6 AWG (13.3 mm²)6.45 mm32.71 mm²182 kg/km3/4" EMT (max 4)
4 AWG (21.2 mm²)8.23 mm53.16 mm²285 kg/km1" EMT (max 4)
2 AWG (33.6 mm²)9.75 mm74.71 mm²438 kg/km1-1/4" EMT (max 5)
1/0 AWG (53.5 mm²)12.34 mm119.7 mm²688 kg/km1-1/2" EMT (max 4)
2/0 AWG (67.4 mm²)13.51 mm143.5 mm²858 kg/km2" EMT (max 6)
4/0 AWG (107.2 mm²)16.31 mm208.8 mm²1342 kg/km2" EMT (max 4)
250 kcmil (127 mm²)18.06 mm256.1 mm²1585 kg/km2-1/2" EMT (max 5)
500 kcmil (253 mm²)24.13 mm456.8 mm²3095 kg/km3" EMT (max 5)

Enregistrez ce calcul et exportez-le en PDF avec l’app Vexten.Google PlayApp Store

Questions fréquentes

Quelles caractéristiques techniques regroupe le tableau dimensions des câbles ?

Tableaux de référence des diamètres et poids des câbles. Il rassemble 12 entrées de référence classées selon Section THHN/THWN-2, Diamètre Ext., Section Totale, Masse Cuivre et Remplissage EMT 40% pour une consultation rapide en bureau d’études ou sur site.

Comment rechercher et choisir la bonne valeur dans dimensions des câbles ?

Repérez d’abord la colonne section THHN/THWN-2 (couvrant de 14 AWG (2.08 mm²) à 500 kcmil (253 mm²)) ou saisissez une désignation, une section ou une valeur dans le champ de filtre pour isoler les lignes correspondantes.

Quels critères pratiques vérifier lors de l’utilisation de dimensions des câbles ?

Il convient de vérifier simultanément le courant admissible corrigé selon la température ambiante et le groupement ainsi que la chute de tension en bout de ligne afin d’éviter tout échauffement.