Dimensiones de Cables

Tablas de referencia de diámetros y pesos de cables.

12 filas

Calibre THHN/THWN-2Diámetro Ext. (OD)Área Total AisladaMasa Cobre Aprox.Guía Rápida EMT 40%
14 AWG (2.08 mm²)2.82 mm6.26 mm²31 kg/km1/2" EMT (max 12)
12 AWG (3.31 mm²)3.30 mm8.58 mm²46 kg/km1/2" EMT (max 9)
10 AWG (5.26 mm²)4.17 mm13.61 mm²73 kg/km1/2" EMT (max 5)
8 AWG (8.37 mm²)5.49 mm23.61 mm²118 kg/km3/4" EMT (max 5)
6 AWG (13.3 mm²)6.45 mm32.71 mm²182 kg/km3/4" EMT (max 4)
4 AWG (21.2 mm²)8.23 mm53.16 mm²285 kg/km1" EMT (max 4)
2 AWG (33.6 mm²)9.75 mm74.71 mm²438 kg/km1-1/4" EMT (max 5)
1/0 AWG (53.5 mm²)12.34 mm119.7 mm²688 kg/km1-1/2" EMT (max 4)
2/0 AWG (67.4 mm²)13.51 mm143.5 mm²858 kg/km2" EMT (max 6)
4/0 AWG (107.2 mm²)16.31 mm208.8 mm²1342 kg/km2" EMT (max 4)
250 kcmil (127 mm²)18.06 mm256.1 mm²1585 kg/km2-1/2" EMT (max 5)
500 kcmil (253 mm²)24.13 mm456.8 mm²3095 kg/km3" EMT (max 5)

Guarda el cálculo y expórtalo en PDF con la app Vexten.Google PlayApp Store

Preguntas frecuentes

¿Qué especificaciones técnicas incluye la tabla de dimensiones de cables?

Tablas de referencia de diámetros y pesos de cables. Reúne 12 entradas comparativas organizadas según Calibre THHN/THWN-2, Diámetro Ext. (OD), Área Total Aislada, Masa Cobre Aprox. y Guía Rápida EMT 40% para consulta rápida en diseño y mantenimiento.

¿Cómo buscar y seleccionar el valor adecuado en dimensiones de cables?

Localiza primero la columna de calibre THHN/THWN-2 (que abarca desde 14 AWG (2.08 mm²) hasta 500 kcmil (253 mm²)) o escribe cualquier código, calibre o magnitud en el buscador superior para filtrar las filas coincidentes al instante.

¿Qué criterios prácticos tener en cuenta al aplicar datos de dimensiones de cables?

Conviene comprobar simultáneamente la capacidad térmica del conductor según la temperatura ambiente y el agrupamiento, junto con la caída de tensión en el extremo receptor para evitar sobrecalentamiento y pérdidas de energía.