Solar PV String Max Voc

Calculates peak inverter DC input voltage at record minimum winter design temperature.

-
Vocmax =—

Enter your values to calculate instantly.

Vocmax = N · Vocstc · [1 + (βvoc / 100) · (Tmin - 25)]

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

How it’s calculated

Vocmax=N⋅Vocstc⋅[1+(βvoc/100)⋅(Tmin⁡−25)]Vocmax = N \cdot Vocstc \cdot [1 + (\beta voc / 100) \cdot (T_{\mathrm{\min}} - 25)]
Vocmax
Solar PV String Max Voc · V / kV / mV / µV
N
Number of Modules in Series · -
Voc
Open-Circuit Voltage at STC · V / kV / MV / mV
β
Voc Temperature Coefficient · %/°C / %/K / %/°F
Tmin
Minimum Design Temperature · °C / K / °F / °R

Questions

What is the formula for solar PV string max voc and what does each variable mean?

The governing equation is Vocmax = N · Vocstc · [1 + (βvoc / 100) · (Tmin - 25)], solving for Vocmax from N (number of modules in series, -), Voc (Open-Circuit voltage at STC, V), β (voc temperature coefficient, %/°C) and Tmin (minimum design temperature, °C). Calculates peak inverter DC input voltage at record minimum winter design temperature.

Which input and output units can you select for solar PV string max voc?

Every parameter includes metric and imperial unit selectors: N [-]; Voc [V, kV, MV, mV, µV]; β [%/°C, %/K, %/°F]; Tmin [°C, K, °F, °R]. The solver normalizes all scales automatically before evaluating the equation and lets you switch the output Vocmax across V, kV, mV, µV, MV.

When is the solar PV string max voc formula used in electrical engineering?

Normalize all unit prefixes before solving, keep actual power dissipation below 50–60 % of component power ratings for thermal reliability, and account for standard manufacturing tolerances.