IEC Motor Duty Types (S1–S10)

Duty cycles S1 through S10, cyclic duration factor, and thermal loading profiles for electric motors.

14 rows

Duty TypeNameplate MarkingCyclic Duration FactorThermal Derating
S1S1 — 100 %100 %1.00× Pn
S2S2 30 min10 / 30 / 60 / 90 min1.15 – 1.40× Pn
S3S3 40 %15 / 25 / 40 / 60 %1.10 – 1.35× Pn
S4S4 25 % 120 c/h15 – 60 % (FI)0.75 – 0.95× Pn
S5S5 25 % 180 c/h15 – 60 % (F + R)0.65 – 0.85× Pn
S6S6 40 %15 / 25 / 40 / 60 %1.15 – 1.35× Pn
S7S7 300 c/h100 % (F + R)0.60 – 0.80× Pn
S8S8 2/4/8p100 % (Δn / ΔP)0.70 – 0.90× Pn
S9S9 — VFD0 – 150 % PnI_rms ≤ In
S10S10 Δt / p1 – 4 × (p / Δt)TL ≤ 1.00
CONTCONT — SF 1.15100 %1.00 – 1.15× HP
TEMP30 / 60 MIN5 / 15 / 30 / 60 min1.20 – 1.50× HP
INTINT — 15 / 60 %15 – 60 %0.80 – 1.25× HP
VARINV CT / VTCT 10:1 / VT 20:1I_rms ≤ FLA

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Questions

What technical specifications does the IEC motor duty types table include?

Duty cycles S1 through S10, cyclic duration factor, and thermal loading profiles for electric motors. It compiles 14 reference entries organized across Duty Type, Nameplate Marking, Cyclic Duration Factor and Thermal Derating for fast lookup during design and field maintenance.

How do you look up and select the right rating in IEC motor duty types?

Locate the target duty type in the first column (spanning from S1 through VAR) or type any designation, size, or rating into the search bar above to filter matching rows instantly.

What practical factors should you check when applying IEC motor duty types data?

Distinguish mechanical shaft output from electrical input power by accounting for efficiency and power factor, and allow for locked-rotor starting inrush when sizing feeders and protection.

Related buying guides