Generator Size (kVA, kW & ATS)

Combine running load and largest motor or A/C starting surge to size the standby generator (kVA & kW), transfer switch (ATS), and copper feeder.

W
W
%
System
—

Enter your values to calculate instantly.

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

Quick standby generator sizing chart by home & business profile

Backup scenarioRunning loadRecommended (kW)Rating (kVA @ 0.8 PF)ATS @ 220 V
Essentials (fridge, lights, Wi-Fi, TV)1.8 kW4 kW5 kVA25 A
Standard home + 12k BTU A/C + water pump4.2 kW8 kW10 kVA50 A
Full home + 2 A/C units + appliances7.8 kW12 kW15 kVA40 A
Small shop / clinic / office12.5 kW20 kW25 kVA70 A
Workshop / bakery / restaurant24 kW40 kW50 kVA150 A

How it’s calculated

Never size a generator to run at 100% nameplate load: keep 20–25% headroom so it operates in its 70–80% sweet spot and handles fridge, well-pump, and A/C compressor starting surges. At 0.8 PF, a 10 kVA generator delivers 8 kW.

SkVA=(Prun+0.5 Psurge)⋅(1+m)0.8⋅1000S_{\text{kVA}} = \dfrac{(P_{\text{run}} + 0.5\,P_{\text{surge}}) \cdot (1 + m)}{0.8 \cdot 1000}

Questions

What size generator do I need for a house with 1 or 2 air conditioners?

For a home with fridge, lights, water pump, and one 12,000 BTU inverter A/C, a 7.5–10 kVA (6–8 kW) generator is typically sufficient. For two A/C units plus full household loads, plan on 12.5–15 kVA (10–12 kW).

Is a transfer switch required when connecting a generator to a home panel?

Yes, always. Connecting a generator without a mechanical interlock or transfer switch (manual or ATS) can backfeed the utility line, endangering utility lineworkers and destroying the generator when grid power returns.