How it’s calculated
Motor branch-circuit conductors must be sized to at least 125% of full-load amps (FLA). Set the thermal overload relay to exact nameplate FLA (or 1.15× for SF ≥ 1.15), and select an AC-3 contactor ≥ FLA.
Questions
How many amps does a 5 HP or 10 HP three-phase motor draw?
A 5 HP (3.7 kW) 3-phase motor draws roughly 13.4 A at 220 V, 7.4 A at 400 V, and 6.1 A at 480 V. A 10 HP (7.5 kW) motor draws roughly 26.8 A at 220 V, 14.7 A at 400 V, and 12.3 A at 480 V.
Why is the motor circuit breaker rated higher than the overload relay?
Because a motor draws 6–8× FLA during startup for several seconds. The breaker (inverse-time or Curve D) rides through inrush and clears short circuits, while the overload relay protects the windings against sustained overcurrent.