Get the complete direct-on-line (DOL) starter bill of materials from HP or kW: full-load current, overload relay range, AC-3 contactor, breaker, and 125% wire.

Supply
%
—

Enter your values to calculate instantly.

Save this calculation and export it as a PDF with the Vexten app.Google PlayApp Store

Share this calculation

WhatsApp

Quick 3-phase motor FLA, contactor & wire size chart (0.5 HP to 100 HP)

Motor PowerFLA 3Φ 220 VFLA 3Φ 400 VFLA 3Φ 480 VAC-3 Contactor (400 V)Cu Wire @ 400 V
0.5 HP (0.37 kW)1.6 A0.9 A0.7 A9 A14 AWG · 1.5 mm²
1 HP (0.75 kW)3.1 A1.7 A1.4 A9 A14 AWG · 1.5 mm²
2 HP (1.49 kW)6.3 A3.4 A2.9 A9 A14 AWG · 1.5 mm²
3 HP (2.24 kW)8 A4.4 A3.7 A9 A14 AWG · 1.5 mm²
5 HP (3.73 kW)13.4 A7.4 A6.1 A9 A14 AWG · 1.5 mm²
7.5 HP (5.59 kW)20.1 A11 A9.2 A18 A14 AWG · 1.5 mm²
10 HP (7.46 kW)26.8 A14.7 A12.3 A18 A12 AWG · 2.5 mm²
15 HP (11.19 kW)37.1 A20.4 A17 A25 A10 AWG · 4 mm²
20 HP (14.91 kW)49.4 A27.2 A22.7 A32 A8 AWG · 6 mm²
25 HP (18.64 kW)61.8 A34 A28.3 A40 A8 AWG · 10 mm²
30 HP (22.37 kW)74.2 A40.8 A34 A50 A6 AWG · 16 mm²
40 HP (29.83 kW)96.2 A52.9 A44.1 A65 A4 AWG · 16 mm²
50 HP (37.29 kW)120.3 A66.2 A55.1 A80 A4 AWG · 25 mm²
75 HP (55.93 kW)180.4 A99.2 A82.7 A115 A1 AWG · 50 mm²
100 HP (74.57 kW)240.6 A132.3 A110.3 A150 A2/0 AWG · 70 mm²

How it’s calculated

Motor branch-circuit conductors must be sized to at least 125% of full-load amps (FLA). Set the thermal overload relay to exact nameplate FLA (or 1.15× for SF ≥ 1.15), and select an AC-3 contactor ≥ FLA.

IFLA=PkW⋅1000k⋅V⋅η⋅cos⁡φ,Icable=1.25⋅IFLAI_{\text{FLA}} = \dfrac{P_{\text{kW}} \cdot 1000}{k \cdot V \cdot \eta \cdot \cos\varphi}, \qquad I_{\text{cable}} = 1.25 \cdot I_{\text{FLA}}

Questions

How many amps does a 5 HP or 10 HP three-phase motor draw?

A 5 HP (3.7 kW) 3-phase motor draws roughly 13.4 A at 220 V, 7.4 A at 400 V, and 6.1 A at 480 V. A 10 HP (7.5 kW) motor draws roughly 26.8 A at 220 V, 14.7 A at 400 V, and 12.3 A at 480 V.

Why is the motor circuit breaker rated higher than the overload relay?

Because a motor draws 6–8× FLA during startup for several seconds. The breaker (inverse-time or Curve D) rides through inrush and clears short circuits, while the overload relay protects the windings against sustained overcurrent.