Medium voltage switchgear partial discharge diagnosis using TEV and ultrasonic sensors

Introduction and Theoretical Framework of Partial Discharges in Medium-Voltage Switchgear

The operational reliability of medium-voltage (MV) power distribution systems and switchgear depends critically on the integrity of their solid, liquid, and gaseous insulation systems. Partial discharges (PD) constitute the most reliable precursor indicator of dielectric degradation and the inescapable prelude to catastrophic failure via internal arcing. From the perspective of dielectric materials physics, a partial discharge is a localized electrical breakdown phenomenon that does not completely bridge the electrodes across which the electric field is applied. These discharges occur predominantly within voids or gaseous cavities embedded in solid dielectrics (for example, epoxy resin or XLPE insulation), at the interface between different insulating materials (surface tracking and field shedding), or in the vicinity of high-voltage conductors subjected to highly non-uniform electric fields (corona effect).

To comprehend the mathematical genesis of partial discharges within cavities, the defect is modeled as a parasitic capacitor in series within an equivalent capacitive network. Let CcC_c be the capacitance of the gas-filled cavity, CbC_b be the capacitance of the healthy dielectric in series with the cavity, and CaC_a be the capacitance of the remainder of the unaffected insulation. When the alternating voltage applied to the medium-voltage switchgear cell reaches a threshold value, the local electric field EcE_c inside the cavity exceeds the dielectric strength of the gas contained within it (EcritEcrit), triggering an avalanche ionization process. The analytical condition for the initiation of partial discharge is given by:

Ec=εr⋅Vcavδcav≥(β⋅p⋅d)PaschenE_c = \frac{\varepsilon_r \cdot Vcav}{\delta_{cav}} \geq ( \beta \cdot p \cdot d )_{Paschen}

Where εr\varepsilon_r is the relative permittivity of the surrounding dielectric material, VcavVcav is the voltage drop across the cavity, δcav\delta_{cav} is the linear dimension of the cavity, and the right-hand term represents Paschen's law for the breakdown strength of the gas as a function of pressure pp and the inter-electrode gap distance of the cavity dd, with β\beta being a gas-specific constant. During the discharge event, which occurs on a nanosecond timescale, the cavity is momentarily short-circuited, provoking an instantaneous charge redistribution on the terminal electrodes of the insulation system. This rapid charge transfer induces a transient current pulse i(t)i(t) detectable in the external circuits, whose waveform is described by the Ramo-Shockley charge-integration equation:

i(t)=q0⋅vd⋅∇ϕ(r(t))i(t) = q_0 \cdot v_d \cdot \nabla \phi(r(t))

Where q0q_0 is the generated free charge, vdv_d is the drift velocity of the electrons and carriers in the electric field, and ϕ\phi is the electrostatic weighting function of the collecting electrode. In the context of medium-voltage switchgear utilizing Air-Insulated Switchgear (AIS) or Sulfur Hexafluoride Gas-Insulated Switchgear (GIS/SIMO), the presence of PD generates multiple secondary physical phenomena of diverse nature: radiofrequency electromagnetic waves that capacitively couple to the external metallic structure (giving rise to Transient Earth Voltages or TEV), high-frequency acoustic pressure and ultrasonic waves due to the thermal and mechanical expansion of the gas or surrounding solid, and chemical reactions resulting from decomposition byproducts (such as hydrofluoric acid in GIS cells due to the degradation of SF6SF₆). The early detection and localization of these phenomena require the simultaneous application of non-intrusive or minimally intrusive sensor technologies capable of operating in electromagnetically hostile environments without interrupting the continuity of electrical service.

Physical and Electromechanical Principles of TEV (Transient Earth Voltage) Sensors

Transient Earth Voltages (TEV) represent a high-frequency electromagnetic propagation mechanism that arises directly as a consequence of a partial discharge occurring within the closed metallic compartment of a medium-voltage switchgear cell. When a PD occurs in the internal insulation (for example, in a bushing, an epoxy busbar support, or a voltage transformer), the rapid injection of transient current generates an electromagnetic pulse inside the shielded metallic enclosure. This pulse propagates through the internal dielectric space in the form of Transverse Electromagnetic (TEM) waves traveling at the speed of light toward the metallic walls of the enclosure.

Upon incidence of the electromagnetic wave on the internal surface of the metallic enclosure, the associated current attempts to flow toward the exterior of the housing. However, due to the skin effect and the inherent inductance of the steel or aluminum sheets of the switchgear, the high-frequency current experiences a finite surface impedance. This causes an instantaneous transient potential drop between the inner and outer faces of the metallic enclosure. The resulting voltage on the external surface of the switchgear cell is termed the Transient Earth Voltage (TEV). Mathematically, the surface current density JsJ_s and the tangential magnetic field HtH_t at the metal boundary are related via the complex surface impedance Zs(ω)Z_s(\omega):

Zs(ω)=j⋅ω⋅μ0⋅μrσZ_s(\omega) = \sqrt{\frac{j \cdot \omega \cdot \mu_0 \cdot \mu_r}{\sigma}}

Where ω\omega is the angular frequency of the transient, μ0\mu_0 is the magnetic permeability of free space, μr\mu_r is the relative permeability of the cell's steel or aluminum, and σ\sigma is the electrical conductivity of the material. The TEV voltage measured at a point on the exterior surface of the cell is the line integral of the tangential electric field generated by this current across the thickness of the metal plate. TEV capacitive sensors are designed to capture this surface electric field without requiring direct galvanic connection to the high-voltage circuit.

The TEV sensor typically consists of a circular metallic plate isolated from the switchgear housing by a high-permittivity dielectric and capacitively coupled to the outer surface of the metallic structure. The equivalent circuit structure of the TEV measurement system is modeled as a high-frequency capacitive voltage divider. Let CsenCsen be the capacitance between the sensor and the cell surface, and RtermRterm be the termination resistance of the acquisition instrument (typically 50 Ω50\,\Omega). The frequency domain transfer function of the TEV sensor is expressed as:

HTEV(s)=Vout(s)Vin(s)=s⋅Rterm⋅Csen1+s⋅Rterm⋅(Csen+Cstray)HTEV(s) = \frac{Vout(s)}{Vin(s)} = \frac{s \cdot Rterm \cdot Csen}{1 + s \cdot Rterm \cdot (Csen + Cstray)}

This configuration makes it possible to capture pulses with rise times on the order of nanoseconds (typically between 2 ns2\, ns and 10 ns10\, ns) and amplitudes varying from a few millivolts to several hundred millivolts. Nevertheless, the correct interpretation of TEV readings requires overcoming significant technical challenges associated with signal attenuation, multimodal propagation within complex switchgear structures, and the ubiquitous presence of ambient electromagnetic noise (such as radiofrequency interference from telecommunication stations, thyristor switching, or adjacent variable-speed drives). For this reason, modern measurement equipment incorporates digital wave filtering algorithms (Wavelet Transforms), fundamental power frequency synchronization (Phase Resolved Partial Discharge - PRPD patterns), and temporal discrimination to separate genuine PD pulses from multiple reflections and white noise.

Ultrasonic Acoustics and Mechanical Wave Propagation Phenomenology

While TEV sensors detect the electromagnetic signature of partial discharges occurring within the enclosed interior of metallic compartments, ultrasonic acoustics complements the diagnostic strategy by capturing the mechanical pressure waves generated by the discharge. When a partial discharge occurs in air (surface corona effect or discharges in open micro-cracks exposed to air or gas interfaces within AIS cells), or when the shock wave generated by a PD inside a solid medium is transmitted toward the enclosure, acoustic waves are generated spanning from the audible range up to deep ultrasonic spectra (typically between 20 kHz20\, kHz and 300 kHz300\, kHz).

The utilization of the ultrasonic spectrum is fundamental in industrial environments because acoustic waves in this frequency range suffer severe attenuation in ambient air, guaranteeing that background operational substation noise (such as transformer hum at 50/60 Hz50/60\, Hz and its mechanical harmonics, fan noise, or human voice) does not interfere with the measurement. The acoustic pressure p(r,t)p(r, t) generated by a point discharge of the corona type obeys the three-dimensional acoustic wave equation with a volumetric source term Q(t)Q(t):

∇2p(r,t)−1vs2∂2p(r,t)∂t2=−ρ0∂Q(t)∂t\nabla^2 p(r, t) - \frac{1}{v_s^2} \frac{\partial^2 p(r, t)}{\partial t^2} = -\rho_0 \frac{\partial Q(t)}{\partial t}

Where vsv_s is the speed of sound in the propagation medium (approximately 343 m/s343\, m/s in air at 20∘C20^\circ C, and on the order of 2500 m/s2500\, m/s to 5000 m/s5000\, m/s in solid materials such as epoxy resins and metals), and ρ0\rho_0 is the volumetric density of the medium. The amplitude of the acoustic pressure decays inversely with distance rr from the source due to spherical geometric divergence, and exponentially due to viscous and thermal absorption of the medium, described by the acoustic attenuation coefficient α(ω)\alpha(\omega):

p(r)=p0⋅r0r⋅e−α(ω)⋅(r−r0)p(r) = p_0 \cdot \frac{r_0}{r} \cdot e^{-\alpha(\omega) \cdot (r - r_0)}

In the design of ultrasonic sensors for medium-voltage switchgear, piezoelectric transducers based on advanced lead zirconate titanate (PZT) ceramics or piezoelectric polymer composites (PVDF) are primarily employed. These transducers are tuned to resonate at specific frequencies, typically around 40 kHz40\, kHz. The transducer converts the incident mechanical pressure into a proportional electrical signal via the direct piezoelectric effect, modeled by the coupled electro-elastic constitutive equations:

D=dσ⋅T+εT⋅ED = d^\sigma \cdot T + \varepsilon^T \cdot E
S=sE⋅T+(dt)σ⋅ES = s^E \cdot T + (d^t)^\sigma \cdot E

Where DD is the electric displacement vector, TT is the mechanical stress tensor, SS is the strain tensor, EE is the induced electric field, dσd^\sigma is the matrix of piezoelectric constants, εT\varepsilon^T is the permittivity under constant stress, and sEs^E is the elastic compliance under constant field. The application of ultrasound requires proper physical coupling between the sensor and the switchgear surface, either through direct contact using acoustic gel or via metallic or polymeric waveguides designed to penetrate through gaskets and ventilation louvers without compromising the IP (Ingress Protection) rating of the medium-voltage switchgear cell.

Architecture and Methodology of Multimodal Localization (TEV + Ultrasound)

The synergistic combination of TEV sensors and ultrasonic acoustics constitutes a multimodal diagnostic methodology that overcomes the inherent limitations of each technology when deployed in isolation. While the TEV sensor offers high sensitivity to detect internal discharges (within the volume of solid or liquid insulation) but exhibits lower spatial precision due to the complex propagation of electromagnetic waves in the metallic enclosure, the ultrasonic sensor provides excellent spatial localization and discrimination of surface or external sources, yet is incapable of detecting discharges deeply embedded within thick epoxy resin blocks or closed gas compartments lacking direct acoustic propagation paths.

The architecture of the inspection and monitoring system is based on the temporal and amplitude correlation of signals acquired simultaneously by both channels. The multimodal signal processing workflow is governed by the following analytical sequence:

  • Synchronous Acquisition: The TEV and ultrasonic channels are simultaneously digitized using a high-sampling-rate Analog-to-Digital Converter (ADC) (typically ≥100 MS/s\ge 100\, MS/s) to guarantee a temporal resolution below 10 ns10\, ns.
  • Feature Extraction: Key statistical parameters per power cycle are calculated, including peak value (VpeakVpeak), root mean square (RMSRMS), pulse repetition rate (PRPD - Pulses per Second), and integrated signal envelope energy.
  • Data Fusion and Defect Classification: Through machine learning algorithms or IEC-standard-based decision trees, the combined signatures are classified into specific fault typologies (Corona, Surface Discharges, Internal Voids, Floating Components).

For fine spatial localization of the discharge source within a switchgear panel, the Time Difference of Arrival (TDOA) technique is implemented utilizing multiple ultrasonic sensors distributed in a geometric array on the exterior surface of the switchgear cell. Let (xi,yi,zi)(x_i, y_i, z_i) be the coordinates of sensor ii, and (xs,ys,zs)(x_s, y_s, z_s) be the unknown coordinates of the PD source. The arrival time of the acoustic signal at sensor ii with respect to the reference sensor 11 is governed by the system of non-linear hyperbolic equations:

c⋅(ti−t1)=(xi−xs)2+(yi−ys)2+(zi−zs)2−(x1−xs)2+(y1−ys)2+(z1−zs)2c \cdot (t_i - t_1) = \sqrt{(x_i - x_s)^2 + (y_i - y_s)^2 + (z_i - z_s)^2} - \sqrt{(x_1 - x_s)^2 + (y_1 - y_s)^2 + (z_1 - z_s)^2}

This system is solved computationally via iterative numerical optimization methods, such as the Levenberg-Marquardt non-linear least squares algorithm, enabling the localization of the discharge source with millimeter precision within the three-dimensional plane of the switchgear compartment.

Forensic Engineering of Failures in Medium-Voltage Switchgear Caused by Partial Discharges

Forensic failure analysis in medium-voltage switchgear reveals that a significant proportion of unscheduled outages originates from degradation processes initiated by partial discharges that were not detected in time. The most critical failure modes manifest in specific components of the switchgear, presenting well-defined phenomenological characteristics:

Solid Epoxy Resin Insulation (Instrument Transformers and Supports)

Current transformers (CT) and voltage transformers (VT) encapsulated in epoxy resin are highly vulnerable to the formation of micro-cavities during the factory thermal polymerization process or due to operational thermo-mechanical stresses caused by severe load cycles. Continuous partial discharges in these voids generate erosion via ionic bombardment and chemical decomposition of the polymer through the scission of carbon bonds, releasing carbon monoxide gas and creating branched carbonized channels known as "tracking" or electrical trees. When the length of these electrical trees bridges the remaining insulation distance, dielectric puncture and the consequent phase-to-earth short circuit occur.

Underground Cable Terminations and Splices in the Cable Compartment

In the cable entry compartment of the switchgear, poor workmanship in the assembly of heat-shrinkable or premolded terminations generates air voids at the interface between the main cable insulation (XLPE) and the termination body. The tangential electric field in this zone rapidly exceeds the dielectric strength of the entrapped air. The resulting surface discharges degrade the stress control semiconductor, causing layer delamination and the formation of carbonized conductive tracks that inevitably lead to disruptive interphase arcing or arcing toward the grounded metallic structure.

Busbars and Joints in AIS and GIS Systems

In Air-Insulated Systems (AIS), insufficient clearances between busbars or the presence of particulate contaminants (metallic dust, filings, or moisture) on supporting insulators generate non-uniform fields that enhance corona discharges and surface tracking. In GIS switchgear, the presence of free metallic particles within the SF6SF₆ gas acts as a local field amplifier; under the influence of the alternating electric field, these particles levitate and bounce, provoking continuous partial discharges that degrade the insulating capacity of the gas and generate corrosive byproducts attacking elastomeric seals.

MV Switchgear Component PD Failure Mechanism Critical Electrical Parameters (IEC / IEEE) Dielectric and Operational Consequences
Epoxy Voltage Transformers (VT) Electrical treeing due to internal voids in the solid dielectric. Maximum discharge level < 10 pC at 1.2 Um/√3 (IEC 60044-2) Massive internal short circuit, resin tank explosion, main protection tripping.
XLPE Cable Terminations Surface discharges due to stress control failures and entrapped air. Maximum tangential stress < 2.5 kV/mm; PD < 5 pC (IEEE 48) External phase-to-earth arc, destruction of cable compartment, prolonged downtime.
AIS Busbars Corona effect and surface discharges due to contamination and humidity. Surface gradient < 15 kV/cm; TEV intensity < 20 dBmV Interphase fault, degradation of insulating supports, puncture of metal partitions.
GIS Compartments (SF6) Free metallic particles and conical spacer defects. Leakage rate < 0.5% annual; Operating PD level < 5 pC (IEC 62271-203) Loss of gas dielectric strength, high-energy internal arc fault ignition (Internal Arc Fault IAC FLR).

Design Strategies, Mitigation, and International Normative Criteria

The effective mitigation of partial discharges in medium-voltage switchgear requires the rigorous application of international design and manufacturing standards, such as IEC 62271-200 (for metal-enclosed switchgear up to 52 kV) and IEEE C37.20.2. Design engineers must ensure that maximum electric fields at any point in the insulation system do not exceed the critical partial discharge inception voltage (PDIV) thresholds.

Mathematically, the optimization of the geometric design of electrodes and field-grading shielding screens is formulated by solving Laplace's equation for electrostatic potential Φ\Phi:

∇⋅(ε(r)∇Φ)=0\nabla \cdot (\varepsilon(r) \nabla \Phi) = 0

Subject to Dirichlet and Neumann boundary conditions on the surfaces of conductors and metallic shields. Mitigation strategies implemented during the detailed engineering phase comprise:

  • Geometric Stress Control: Strict enforcement of minimum curvature radii at busbar junctions and metallic profiles to prevent electric field intensification in accordance with Rogowski or Bruce plate shape factors.
  • Surface Treatment and Semiconductor Coatings: Utilization of extruded semiconductor layers in cable terminations and joints to ensure a gradual transition of electrical potential and eliminate interstitial gaseous voids.
  • Vacuum Casting Technology: Rigorous control of pressure and temperature during the casting process of epoxy resin components to eliminate the presence of microscopic air bubbles larger than 50 μm50\,\mu m.
  • Continuous On-Line Condition Monitoring: Permanent installation of capacitively coupled TEV sensors and UHF (Ultra High Frequency) sensors in critical switchgear cells, integrated into SCADA systems via gateways utilizing IEC 61850 protocols for real-time trend analysis of partial discharges.

Practical Application and Engineering Analysis via Vexten Suite

To illustrate the practical application of the theoretical and normative concepts discussed, an analytical case study evaluated using advanced calculation tools from the Vexten Suite platform—oriented toward the design and diagnostics of medium-voltage industrial electrical systems—is presented.

Short-Circuit Current Modeling and Electrodynamic Stresses (IEC 60909 / IEEE 141)

A 13.8 kV13.8\, kV medium-voltage switchgear cell is evaluated with an initial symmetrical three-phase short-circuit current Ik′′′=31.5 kAI'_{k''} = 31.5\, kA for a duration of 1 s1\, s. The maximum electrodynamic stresses on the epoxy resin insulating supports holding the busbars are calculated via the force per unit length F′F^\prime between parallel conductors:

F′=μ02π⋅i1(t)⋅i2(t)d=4π×10−72π⋅(2.5⋅2⋅31.5×103)20.15≈6.61 kN/mF^\prime = \frac{\mu_0}{2\pi} \cdot \frac{i_1(t) \cdot i_2(t)}{d} = \frac{4\pi \times 10^{-7}}{2\pi} \cdot \frac{(2.5 \cdot \sqrt{2} \cdot 31.5 \times 10^3)^2}{0.15} \approx 6.61\, kN/m

This severe mechanical stress, combined with the presence of internal micro-defects and pre-existing partial discharges, accelerates the thermo-mechanical fatigue of the insulating material, drastically reducing the Remaining Useful Life (RUL) of the component.

Cable Sizing and Harmonic Derating (IEC 60287 / NEC 310)

In the cable compartment of a feeder cell supplying a Variable Frequency Drive (VFD), the presence of high-frequency harmonic currents induces supplementary losses due to skin and proximity effects in the copper conductors. For a 240 mm2240\, mm^2 XLPE cable with a nominal fundamental current IL=400 AI_L = 400\, A and a total current harmonic distortion (THDiTHD_i) of 30%30\%, the harmonic reduction factor KharmKharm calculated in accordance with IEC 60287 is determined by:

Kharm=(1+∑h=2nMh⋅(IhI1)2)−1/2Kharm = \left( 1 + \sum_{h=2}^{n} M_h \cdot \left(\frac{I_h}{I_1}\right)^2 \right)^{-1/2}

Where MhM_h is the supplementary loss factor for harmonic hh. Assuming an equivalent loss factor resulting in a derating factor Kharm=0.88Kharm = 0.88, the corrected ampacity of the cable is established at Iz=400⋅0.88=352 AI_z = 400 \cdot 0.88 = 352\, A. This thermal condition elevates the operating temperature of the XLPE insulation above 90∘C90^\circ C, accelerating thermal aging processes and catalyzing partial discharge activity at critical interfaces.

Resonance Mitigation and Power Factor Correction

To avoid the amplification of voltage and current harmonics that exacerbate potential gradients in switchgear components, the system incorporates a medium-voltage capacitor bank tuned with line reactors. The tuning frequency of the LC circuit is calculated via:

fr=f1⋅XcXL=50⋅7≈132.28 Hzf_r = f_1 \cdot \sqrt{\frac{X_c}{X_L}} = 50 \cdot \sqrt{7} \approx 132.28\, Hz

This tuning to harmonic order h=2.65h = 2.65 (typically adjusted for reactors with a 7%7\% detuning factor relative to the 4.74.7 harmonic frequency) prevents parallel resonance conditions with the main distribution transformer's inductance, guaranteeing a clean voltage profile and minimizing transient overvoltages that act as triggering agents for partial discharge events within medium-voltage switchgear.

Conclusions

The integration of non-intrusive detection technologies via TEV sensors and ultrasonic acoustics represents the state of the art in predictive monitoring and diagnostics of medium-voltage switchgear. Comprehensive understanding of the physical phenomenology underlying partial discharges, modeled through rigorous electromagnetic and electroacoustic parameters, enables specialist engineers to identify incipient failure patterns long before irreversible dielectric breakdown occurs. The application of multimodal methodologies, backed by analytical calculation tools from the Vexten Suite and strict compliance with international IEC and IEEE standards, ensures maximum operational availability, personnel safety, and resilience of high-demand industrial electrical distribution networks.