Grid-Forming Inverter Instability and Thermal Derating in Steel Plants

Phenomenology of Instability in Grid-Forming Inverters and Electric Arc Furnaces

The integration of power electronics-based energy resources operating under the Grid-Forming (GFM) control paradigm into heavy industrial networks—specifically those feeding Electric Arc Furnaces (EAFs)—introduces severe transient, harmonic, and dynamic stability challenges. Unlike traditional synchronous machine-based sources, GFM inverters emulate the swing equation of a synchronous machine through virtual control algorithms, such as Active Power-Frequency (P−ωP-\omega) and Reactive Power-Voltage (Q−VQ-V) droop control, or via Virtual Oscillator Control (VOC).

The electric arc furnace constitutes a non-linear, stochastic, and highly fluctuating load. During the initial scrap melting phases, the arc impedance exhibits violent, non-linear variations that generate voltage flicker, severe phase imbalances, and a massive spectrum of low- and high-order interharmonics and harmonics. When an industrial microgrid or a hybrid renewable generation system with GFM inverters directly feeds these contaminated buses, an adverse interaction occurs between the inverter output impedance (characterized by its LCLLCL output filter and the dynamics of its internal current and voltage loops) and the time-variant stochastic admittance of the EAF.

Mathematically, the closed-loop transfer function of the GFM inverter can be expressed by considering its output impedance Zout(s)Z_{ out }(s). Let vinv(s)v_{ inv }(s) be the voltage generated by the inverter bridge and iload(s)i_{ load }(s) be the current demanded by the EAF:

Zout(s)=sLinv+Rinv1+Gc(s)Gd(s)Z_{ out }(s) = \frac{s L_{ inv } + R_{ inv }}{1 + G_c(s) G_d(s)}

Where Gc(s)G_c(s) represents the transfer function of the internal regulating controller and Gd(s)G_d(s) denotes the transport delays associated with digital signal processing (DSP), pulse-width modulation (PWM), and sampling. Loop instability occurs when the ratio between the equivalent network impedance Znet(s)Z_{ net }(s) (dominated by EAF fluctuations) and the inverter output impedance violates the generalized Nyquist stability criterion:

det⁡(I+Zout(s)Yload(s))=0\det\left( I + Z_{ out }(s) Y_{ load }(s) \right) = 0

If the EAF admittance Yload(s)Y_{ load }(s) exhibits regions with negative real parts at frequencies corresponding to the virtual electromechanical modes of the inverter (typically between 1Hz1 Hz and 15Hz15 Hz), sub-synchronous oscillations are triggered, leading to overcurrent tripping or the saturation of the GFM inverter current limiters.

Forensic Failure Analysis in Transformers, Cables, and Switchgear

The collateral effects of GFM loop instability and severe distortion induced by EAFs on the electrical infrastructure of the steel plant manifest through mechanisms of thermal, dielectric, and mechanical fatigue in critical assets.

In furnace and interconnection power transformers, the presence of high-order positive and negative sequence harmonic components generates significant supplemental losses due to eddy currents and stray flux losses in windings and tanks. Additional winding losses due to harmonics are modeled as:

PEC=PEC−R∑h=1hmax⁡(IhI1)2h2PEC = P_{EC-R} \sum_{h=1}^{h_{\max}} \left( \frac{I_h}{I_1} \right)^2 h^2

This quadratic increase with respect to the harmonic order hh accelerates the degradation of cellulosic insulation, causing the formation of gas bubbles (COCO, CO₂)) and drastically reducing the dielectric strength of the insulating oil. Likewise, sub-synchronous modulation stemming from GFM instability generates cyclic electrodynamic mechanical stresses in the windings, inducing radial and axial deformations that culminate in inter-turn short circuits. In the case of medium-voltage switchgear (GIS and AIS switchgear with sulfur hexafluoride SF₆) or vacuum circuit breakers), very fast transient overvoltages (VFTO) and harmonic overvoltages magnified by parallel resonance between filter capacitors and cable parasitic inductances exceed basic insulation levels (BIL). This produces sustained partial discharges in the bushings and circuit breaker joints.

Critical Asset Affected Electrical Parameter Normative Limit (IEEE / IEC) Critical Failure Condition Operational / Dielectric Consequence

GFM-EAF Power Transformer Harmonic Loss Factor (FHL) IEEE C57.110 (FHL≤1.0FHL \le 1.0) Ih/I1>15%I_h / I_1 > 15\% in orders h∈[5,11,13]h \in [5, 11, 13] Loss of service life due to thermal degradation of cellulose; dielectric breakdown.

Medium-Voltage Cables Current-Carrying Capacity IEC 60287 / NEC 310 Harmonic derating factor Kh<0.70K_h < 0.70 Cumulative overheating of XLPE insulation, melting of shields. Vacuum Circuit Breakers (GIS/AIS) Dielectric Recovery Rate IEEE C37.04 / IEC 62271-100 Transient overvoltages dv/dt>10kV/μsdv/dt > 10 kV /\mu s Reignitions and capacitive current interruption failures. GFM Inverter LCL Filters Magnetic Core Temperature IEC 60076-6 Magnetic saturation due to Direct Current component (DC Bias) Uncontrolled core losses, destruction of output inductors.

Derating Calculation Methodology According to IEC 60287 and NEC 310

The correct selection of power conductors interconnecting GFM inverters with the main busbar and the EAF must simultaneously comply with international standards IEC 60287 and the National Electrical Code (NEC 310). The massive presence of harmonics increases Joule effect losses in both the central conductor and metallic screens, demanding a current-carrying capacity reduction factor (derating factor).

According to IEC 60287-1-1 and IEC 60287-2-1, total losses per unit length in a multiconductor cable are calculated using the following expression:

W=I2R′(1+Yc+Ys)+WdW = I^2 R^\prime \left( 1 + Y_c + Y_s \right) + W_d

Where II is the fundamental RMS current, R′R^\prime is the alternating current resistance of the conductor at maximum operating temperature, YcY_c is the skin effect and proximity effect loss factor in the conductor, YsY_s is the metallic screen loss factor, and WdW_d is the dielectric loss in the insulation. In the presence of harmonics, the effective resistance and Joule loss factor are modified by the total harmonic loss factor (HFLHFL):

HFL=∑h=1hmax⁡Mh2Krel(h)HFL = \sum_{h=1}^{h_{\max}} M_h^2 Krel(h)

Where Mh=Ih/I1M_h = I_h / I_1 is the individual harmonic distortion rate and Krel(h)Krel(h) represents the resistance ratio weighting the increase in skin effect resistance at high frequencies (Rac(h)/RdcRac(h) / Rdc). Therefore, the maximum allowable current ImaxImax corrected for harmonics according to IEC 60287 is expressed as:

Imax=I0Δθ−WdT4RdcT1+Rdc(1+Yc)T2+Rdc(1+Yc+Ys)(T3+T4)⋅HFLImax = I_0 \sqrt{\frac{\Delta \theta - W_d T_4}{Rdc T_1 + Rdc(1+Y_c)T_2 + Rdc(1+Y_c+Y_s)(T_3 + T_4) \cdot HFL}}

On the other hand, NEC 310 (specifically in sections concerning feeder conductors in industrial installations with non-linear loads) establishes mandatory adjustment factors when harmonics are predominant. If the three-phase four-wire system feeds loads with a high third-harmonic content and multiples thereof (as occurs in the rectification and modulation of GFM inverters under EAF asymmetry conditions), the neutral conductor is considered an active current-carrying conductor, requiring the derating factor typified in NEC Table 310.15(C)(1). The calculation of the adjusted ampacity IadjustedI_{ adjusted } under NEC 310 is formulated as:

Iadjusted=Itable×Ftemp×Fgrouping×FharmonicsI_{ adjusted } = I_{ table } \times F_{ temp } \times F_{ grouping } \times F_{ harmonics }

Where FharmonicsF_{ harmonics } is derived directly as a function of the total demand distortion or total harmonic current distortion (THDiTHDi) measured at the GFM inverter busbar:

  • For THDi≤15%THDi \le 15\%: Fharmonics=1.00F_{ harmonics } = 1.00
  • For 15%<THDi≤35%15\% < THDi \le 35\%: Fharmonics=0.86F_{ harmonics } = 0.86
  • For 35%<THDi≤50%35\% < THDi \le 50\%: Fharmonics=0.70F_{ harmonics } = 0.70
  • For THDi>50%THDi > 50\%: Fharmonics=0.50F_{ harmonics } = 0.50

Enclosure Thermal Balance via Calculated Forced Dissipation

Grid-Forming power converters and associated control equipment installed in outdoor electrical housings (e-houses) or modular cabinets face extreme thermal loads due to switching losses from silicon carbide (SiC) or silicon (IGBT) semiconductors, coupled with radiated electromagnetic fields and convective dissipation from auxiliary equipment. The design of the HVAC and forced ventilation system must ensure that the internal temperature of the enclosure does not exceed critical component operating limits (Tint≤40∘CT_{ int } \le 40^\circ C), even under maximum solar radiation and full-load nominal losses.

The steady-state thermal balance of an enclosure is defined by the general law of energy conservation:

Ploss+Psolar=Qconv+Qr+QforcedP_{ loss } + P_{ solar } = Q_{ conv } + Qr + Q_{ forced }

Where PlossP_{ loss } is the total power dissipated by the inverters and electrical equipment inside the cabinet, PsolarP_{ solar } is the heat gain from incident solar radiation on the enclosure walls, QconvQ_{ conv } is the heat transferred by natural convection, QrQr is the heat dissipated by thermal radiation from exterior surfaces, and QforcedQ_{ forced } is the heat removal capacity provided by the forced ventilation system or air-to-air / air-to-water heat exchangers.

Internal dissipation power PlossP_{ loss } is calculated by summing semiconductor losses (conduction and switching), LCLLCL filter inductor losses, and internal isolation transformer losses:

Ploss=∑Pcond+∑Psw+∑Pinductor+∑PxfmrP_{ loss } = \sum P_{ cond } + \sum P_{ sw } + \sum P_{ inductor } + \sum P_{ xfmr }

The required volumetric air flow rate VV (m3/hm ^3/ h) to evacuate heat via forced ventilation is determined using the sensible heat psychrometric transfer equation:

V=3.1×(Ploss+Psolar)Tint−TextV = \frac{3.1 \times (P_{ loss } + P_{ solar })}{T_{ int } - T_{ ext }}

Where TintT_{ int } is the maximum allowable internal enclosure temperature (∘C^\circ C), TextT_{ ext } is the maximum design external ambient temperature (∘C^\circ C), and the factor 3.13.1 integrates the heat capacity of air at constant pressure and standard density corrected for altitude.

In steel mill environments characterized by conductive dust, metal vapors, and corrosive gases, open forced ventilation systems are unviable. Therefore, closed air-to-air thermal exchange systems or thermoelectric coolers with redundant precision air conditioning units are implemented, designed to NEMA 4X / IP55 protection grades. The equivalent thermal resistance of the exchanger RthRth (∘C/W^\circ C/W) is calculated as:

Rth=A⋅U1Rth = \frac{A \cdot U}{1}

Where AA is the effective surface heat transfer area of the exchange panels and UU is the overall thermal transfer coefficient of the insulated metal enclosure.

Practical Application and Analysis via Vexten Suite

To validate the theoretical methodologies presented, an exhaustive simulation model is implemented within the advanced calculation environment Vexten Suite (modules Vexten-ShortCircuit IEC 60909 / IEEE 141, Vexten-CableDerating IEC 60287 / NEC 310, and Vexten-PowerQuality & Resonance). The analyzed system comprises an industrial microgrid powered by a 15MVA15 MVA GFM inverter plant coupled to a 33kV33 kV medium-voltage busbar, which simultaneously feeds a 45MVA45 MVA electric arc furnace via a dedicated step-down transformer.

Automated Computational Calculation Example in Vexten Suite

The following input parameters extracted from the industrial project are considered:

  • GFM Inverter Rated Power: Sn=15,000kVAS_n = 15,000 kVA
  • Rated Line-to-Line Voltage: Vn=33kV (phase−phase)V_n = 33 kV \ ( phase-phase )
  • Fundamental Load Current: I1=262.43AI_1 = 262.43 A
  • Total Harmonic Current Distortion (THDiTHDi) measured at EAF bus: 38.5%38.5\%
  • Relevant Harmonic Spectrum (Ih/I1I_h / I_1): 5th (22%22\%), 7th (14%14\%), 11th (8%8\%), 13th (5%5\%)
  • Maximum External Ambient Temperature: Text=48∘CT_{ ext } = 48^\circ C
  • Maximum Allowable Internal Enclosure Temperature: Tint=40∘CT_{ int } = 40^\circ C (Note: Active cooling via heat exchanger is required since Text>TintT_{ ext } > T_{ int }).

Using the Vexten-CableDerating calculation engine, a 3×1×400mm23 \times 1 \times 400 mm ^2 XLPE-insulated aluminum tripolar cable, installed in a perforated tray with direct solar radiation and a grouping of 3 circuits, is evaluated. The base ampacity according to IEC 60287 is I0=510AI_0 = 510 A.

The engine calculates the total harmonic loss factor (HFLHFL) from the input spectrum:

HFL=12(1.0)+(0.22)2(1.05)+(0.14)2(1.10)+(0.08)2(1.20)+(0.05)2(1.30)=1.0528+0.0215+0.0077+0.00325=1.0853HFL = 1^2(1.0) + (0.22)^2(1.05) + (0.14)^2(1.10) + (0.08)^2(1.20) + (0.05)^2(1.30) = 1.0528 + 0.0215 + 0.0077 + 0.00325 = 1.0853

Applying the corresponding reduction factors according to NEC 310 and IEC 60287 within Vexten Suite:

  • Temperature Correction Factor (FtempF_{ temp } for 48∘C48^\circ C): 0.820.82
  • Tray Grouping Factor (FgroupingF_{ grouping }): 0.700.70
  • Harmonic Derating Factor (FharmonicsF_{ harmonics } for THDi=38.5%THDi = 38.5\% per NEC 310): 0.700.70

The resulting actual current-carrying capacity calculated by the software is:

Imax_real=510A×0.82×0.70×0.70=205.17AI_{ max\_real } = 510 A \times 0.82 \times 0.70 \times 0.70 = 205.17 A

Given that the nominal operating current is 262.43A262.43 A, the initially selected cable proves insufficient under the harmonic and thermal conditions of the steel plant. The Vexten Suite optimization algorithm automatically resizes the conductor to a 3×1×630mm23 \times 1 \times 630 mm ^2 section with a reinforced copper screen and optimized correction factor.

Mitigation Strategies Implemented in the Vexten Model

To suppress the GFM control loop instability induced by the stochastic impedance of the EAF, the Vexten Suite stability module prescribes the following modifications to the inverter control architecture:

  • Virtual Impedance Loop: Injection of a resistive-inductive virtual impedance into the GFM inverter voltage loop to damp resonance peaks in the 5Hz5 Hz to 25Hz25 Hz frequency band.
  • Adaptive Droop Gain Scheduling: Real-time dynamic adjustment of P−ωP-\omega droop loop gains as a function of instantaneous bus short-circuit capacity variations (SCRSCR - Short Circuit Ratio), preventing loss of synchronism during transient voltage collapses caused by electric arc ignition.
  • Hybrid Active Power Filters (APF): Installation of a centralized parallel APF system on the 33kV33 kV busbar to compensate for low-order harmonic currents before they penetrate the output terminals of the GFM inverters, reducing overall THDiTHDi below 5%5\% and ensuring strict compliance with IEEE 519 grid codes.

Technical Engineering Conclusions

The joint operation of Grid-Forming inverters and electric arc furnaces in steel plants demands superior analytical rigor compared to conventional electrical systems. Control loop instability is not an isolated phenomenon, but the direct result of interaction between the power electronics-based converter output impedance and the highly non-linear, time-variant EAF admittance. Cable ampacity calculations per IEC 60287 and NEC 310 cannot be limited to fundamental steady-state currents; the inclusion of the harmonic loss factor (HFLHFL) and derating factors for high harmonic content are mandatory to prevent catastrophic insulation failures. Similarly, thermal design of enclosures via calculated forced dissipation and precision active cooling guarantees the preservation of service life for semiconductors and advanced control systems modeled and validated through high-performance engineering platforms such as Vexten Suite.